Communications wiring
Fan Coil CARRIER CORPORATION ©2020
Integration Guide All rights reserved
7
To set the Device Instance number or adjust the Max Masters or Max Info Frames using an Equipment Touch
1 In the Equipment Touch interface, navigate to the Properties Menu screen and click Login.
NOTE The following graphic is generic and not specific to your system.
2 Type Touch for the password and click Done.
3 On the Properties Menu screen, scroll to the bottom of the list and click ET System.
4 On the ET System screen, click Setup.
5 On the Setup screen, click Module Setup.
6 On the Module Setup screen, click Communication.
On the Communication screen, edit the fields as needed: