Communications wiring
Fan Coil CARRIER CORPORATION ©2020
Integration Guide All rights reserved
4
Protocol Overview
You can set the Fan Coil to communicate 1 of 4 different protocols:
• BACnet MS/TP (page 5)
• BACnet ARC156 (page 9)
• N2 (page 13)
• Modbus (page 11)
• LonWorks (page 15)
The default setting is BACnet MS/TP. You set the protocol and baud rate on the Comm Selector DIP switches on
the controller. See table below for specific switch settings.
The third party connects to the controller through the Comm port for BACnet MS/TP, N2, Modbus, and through the
Option Card port for the LonWorks Option Card.
NOTES
• Changing protocol requires no programming or point assignment by the installer or operator.
• Power must be cycled after changing the Comm Selector DIP switches or connecting the LonWorks Option
Card.
Comm Selector DIP switch settings for protocols and baud