Communications wiring
Fan Coil CARRIER CORPORATION ©2020
Integration Guide All rights reserved
5
BACnet MS/TP
To set up the Fan Coil for BACnet MS/TP
The Fan Coil’s latest supported function codes and capabilities are listed on the associated Protocol
Implementation Conformance Statement (PICS), Carrier BACnet PICS website
http://www.bacnetinternational.net/catalog/index.php?m=28.
NOTE This controller counts as a full load on the MS/TP bus.
1 Turn off the power for the Fan Coil by disconnecting power terminals.
2 Using the rotary switches, set a unique address. Set the Tens (10's) switch to the tens digit of the address,
and set the Ones (1's) switch to the ones digit.
EXAMPLE If the controller’s address is 25, point the arrow on the Tens (10's) switch to 2 and the arrow on
the Ones (1's) switch to 5.
10's
1's
1
3
4
5
2
7
8
9
6
0
1
3
4
5
2
7
8
9
6
0
NOTE The Fan Coil recognizes its address only after power has been cycled.
3 Set communications selector for EIA-485.
4 Set DIP switches 1 and 2 for the appropriate communications speed. See table below.
NOTE Use the same baud rate for all devices on the network segment.
Baud Rate
1
2
9,600 bps
Off
Off
19.2 kbps
Off
On
38.4 kbps
On
Off
76.8 kbps
On
On
5 Set the both DIP switches 3 and 4 OFF for BACnet MS/TP.