Start-up
Fan Coil CARRIER CORPORATION ©2020
Integration Guide All rights reserved
18
Use one of the following interfaces to start up, access information, read sensor values, and test the controller.
Field Assistant application -
Runs on a laptop that connects to controller's Local Access port
1
Equipment Touch device -
Connects to controller's Rnet port
2
Temporary or permanent
interface
i-Vu® application
Available for BACnet systems only
System Touch device
Available only for BACnet MS/TP systems.
Wire to a BACnet MS/TP network connector and a 24 Vac power supply
3
Temporary or permanent
interface
1
Requires a USB Link (Part #USB-L).
2
See the Equipment Touch Installation and Setup Guide for detailed instructions.
3
See the System Touch Installation and Setup Guide for detailed instructions.
CAUTION If multiple controllers share power but polarity was not maintained when they were wired, the
difference between the controller's ground and the computer's AC power ground could damage the USB Link and
the controller. If you are not sure of the wiring polarity, use a USB isolator between the computer and the USB
Link. Purchase a USB isolator online from a third-party manufacturer.