EasyManua.ls Logo

Carrier Fan Coil - Page 39

Carrier Fan Coil
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix A: Fan Coil Network Points List
Fan Coil CARRIER CORPORATION ©2020
Integration Guide All rights reserved
35
N2
LonWorks
Point Name
Point
Access
Units
Default
Value
N2
Network
Point
Type
N2
Network
Point
Address
SNVT Type
SNVT Name
Enable
Dehumidification
R
Inactive
Active
BI
9
SNVT_switch(95)
nvoDehmRelay
Filter
R
(0) Normal
(1) Alarm
BI
31
SNVT_switch(95)
nvoFilter
Fire / Smoke
Shutdown
R
(0) Normal
(1) Alarm
BI
32
SNVT_switch(95)
nvoFrShtdwn
Heat Enable
R/W
Disable
Enable
Active (1)
BO
37
SNVT_switch(95)
nviHtEnb
High Space
Temperature
R
(0) Normal
(1) Alarm
BI
35
SNVT_switch(95)
nvoHiSpTemp
Indoor Air Quality
R
(0) Normal
(1) Alarm
BI
33
SNVT_switch(95)
nvoIAQAlm
Low Space
Temperature
R
(0) Normal
(1) Alarm
BI
39
SNVT_switch(95)
nvoLoSpTmp
Occupancy Status
R
Unoccupied
Occupied
BI
18
SNVT_switch(95)
nvoOccStatus
Reheat Enable
R/W
Disable
Enable
Inactive (0)
BO
4
SNVT_switch(95)
nviRehtEnbl
Reset Filter Alarm
R/W
(0) Off
(1) On
Inactive (0)
BO
22
SNVT_switch(95)
nviRstFilAlm
Return Air
Temperature
R
(0) Normal
(1) Alarm
BI
21
SNVT_switch(95)
nvoRatAlm
Setpoint Adjustment
R/W
Disable
Enable
Active (1)
BO
26
SNVT_switch(95)
nviSPAdjEnbl
Shutdown
R/W
Inactive
Active
Inactive (0)
BO
1
SNVT_switch(95)
nviShutdown
Space Relative
Humidity
R
(0) Normal
(1) Alarm
BI
34
SNVT_switch(95)
nvoHiSPRHAlm
Supply Air
Temperature
R
(0) Normal
(1) Alarm
BI
47
SNVT_switch(95)
nvoSATSensor
Supply Fan Failure
R
(0) Normal
(1) Alarm
BI
58
SNVT_switch(95)
nvoSFAlarm
Fan / Speed
R
(1) Off
(2) Low
(3) Med
(4) High
(5) On
ADI
4
SNVT_count_inc(9)
nvoFanSpeed
Optimal Start Type
R/W
(1) None
(2) Temp
Compensated
(3) Learning
Adaptive
2
ADI
20
SNVT_count_inc(9)
nviOptStType

Table of Contents

Related product manuals