11
   
Common CHWS 
Temp
AI7 IOB3 Used for lead lag option
Auto Water Temp 
Reset
AI8 IOB3 User option, 4~20mA
Common CHWR 
Temp
AI9 IOB3 Used for lead lag option
Head Pressure 
Output
AO1 IOB3 Factory option
Guide Vane 2 Output AO3 IOB3
Spare Safety DI3 IOB3 User option, dry contact, 
normal open
Power Request 
Feedback
DI4 IOB3 Marine option
Evaporator Drain 
Valve
DO1 IOB3
Condenser Drain 
Valve
DO2 IOB3
Free Cooling Mode DO3 IOB3 Factory option
Power Request 
Output
DO4 IOB3 Marine option
Entering Evap Water 
Pressure
AI3 IOB4 User option, if IOB4 
installed, same as follows
Leaving Evap Water 
Pressure
AI4 IOB4 User option
Entering Cond Water 
Pressure
AI5 IOB4 User option
Leaving Cond Water 
Pressure
AI6 IOB4 User option
Evap Water Flow 
Measurement
AI8 IOB4 User option, 4~20mA
Conde Water Flow 
Measurement
AI9 IOB4 User option, 4~20mA
Chilled Water 
Pump(Variable)
AO1 IOB4 User option, 4~20mA/0~5V
Condenser Water 
Pump(Variable)
AO2 IOB4 User option, 4~20mA/0~5V
Tower Fan(Variable) AO3 IOB4 User option, 4~20mA/0~5V
Customer Alert DI3 IOB4 Marine option, dry contact
Free Cooling Start 
Switch
DI4 IOB4 Marine option, dry contact
Chilled Water Pump DO1 IOB4 User option
Condenser Water 
Pump
DO2 IOB4 User option
Tower Fan High DO3 IOB4 User option
Tower Fan Low DO4 IOB4 User option
Purge Level Switch 
Low
cDI-01 SIOB User option
Purge Level Switch 
High
cDI-02 SIOB User option
Purge Comp Suction 
Temp
AI-01 SIOB User option
Purge Cond  Valve DO-01 SIOB User option
Purge Comp Valve DO-02 SIOB User option
Purge Pumpout Valve DO-03 SIOB User option
Purge Drainage Valve DO-04 SIOB User option
Purge Regeneration 
Valve
cDO-05 SIOB User option
Purge Discharge 
Valve
cDO-06 SIOB User option
Purge Vaccum Pump DO-07 SIOB User option
Purge Compressor DO-08 SIOB User option
Purge Heater DO-10 SIOB User option
The electrical characteristics of the transmission Cables shall 
be comprised of three conductors, (1.5 Pairs) two signals and 
one ground of 20 AWG or larger with 100% shield plus a 
tinned copper braid (65% coverage), embodied as one of the 
following types is recommended by Carrier: 
 - Belden #8772 (for intra building, 60 deg C)
 - Belden #85240 (high temperature, 150 deg C) 
 - Belden #89418 (plenum cable, 200 deg C) 
When LEN-MODBUS gateway which described in section 
3.1.4 is used in the system, the communication cable for LEN 
and MODBUS sides should also follow this requirement.
The communication cable between ISM and IOB should be 
as far away from high voltage cable and other disturbance 
equipment as possible. The communication cable should be 
as short as possible and should be separated from other 
cables. Making the communication cable go through metal 
shield conduct is preferred.