23
analog input signal provided from any external sensor, 
controller, or other device which is appropriately congured. 
At this type, Degrees Reset At 20 mA shall be congured in 
RESETCFG table.
RESET TYPE 2: REMOTE TEMPERATURE RESET
Reset Type 2 is an automatic water temperature reset based 
on a remote temperature sensor input signal. This function 
can be accessed by the following congurations:
 - Congure the remote temperature at no reset occurs 
(Remote temp –> NO RESET). 
 - Congure the remote temperature at full reset occurs 
(remote temp –> FULL RESET). 
Finally, enter the amount of reset (Deg reset water DT full).
RESET TYPE 3 — CONTROLLED WATER TEMP 
DELTA RESET 
Reset Type 3 is an automatic controlled water temperature 
reset based on heat exchanger temperature difference. This 
function can be accessed by the following congurations:
 - Congure the Controlled water temperature delta T at 
no reset occurs (Controlled Water DELTA T NO 
RESET). 
 - Congure the Controlled water temperature delta T at 
full reset occurs (Controlled Water DELTA T FULL 
RESET). 
 - Finally, enter the amount of reset (Deg reset water DT full).
Capacity control shall provide chilled or condenser water temperature control by modulating the position of the inlet guide 
vane 1, and VFD speed for variable speed compressor based.
If VFD OPTION is set to with VFD, when need to increase capacity, the control will rst try to increase IGV TARGET 
POSITION if it has not reached the travel limit, otherwise increase VFD TARGET SPEED; when need to decrease capacity, 
the control will rst try to decrease VFD TARGET SPEED if it has not reached the minimum VFD speed, otherwise decrease 
IGV TARGET POSITION.
100TRAVEL LIMIT
GUIDE VANES % POSITION
GUIDE VANES AT MAX.
MODULATE VFD
VFD AT START-UP SPEED.
MODULATE GUIDE VANES
STARTUP;
VFD TO START-UP SPEED,
GUIDE VANES CLOSED
GUIDE VANESVFD
STA RT
MIN.
MAX.
VFD% SPEED
0
Guide vane control
The control regulates the guide vane position as determined 
by the Capacity Control function in normal condition and 
other functions in abnormal conditions which include 
capacity inhibit request, capacity decrease request. The guide 
vane actuator is driven by guide vane target position and 
comparing to the actual feedback value.. Guide vane actual 
position is limited to between zero and “GV1 TRAVEL 
LIMIT” which is congured at “Service Conguration” menu. 
When chiller is shutting down or off, guide vane is always 
driven to zero.
VFD speed control
If VFD option is set to NO VFD, or compressor relay is not 
closed, VFD TARGET SPEED will be 0.
From compressor relay is commanded to be closed to the 
end of ramp loading, VFD TARGET SPEED will be set to 
startup speed.
When chiller is running normally, the control will get input 
from capacity control to see whether to change VFD 
TARGET SPEED and how much to change.
When chiller is in shut down process, VFD TARGET SPEED 
will be set to minimum VFD speed.
After the compressor relay is cut off, VFD TARGET SPEED 
will be set to 0.