7
Pressure transducers:
Pressure transducers are used to measure and control the pressures in the unit. These electronic sensors deliver 0 to 5 VDC. 
The transducers can be calibrated through the controller. The pressure transducers are connected to the IOBs.
  
 This transducer measures the pressure of the evaporator. Standard for 19XR2~E/V/D, 19XR6/7 and 19DV
 This transducer measures the pressure of the condenser Standard for 19XR2~E/V/D, 19XR6/7 and 19DV
 This transducer measures the pressure of the economizer Standard for 19XR6/7 
 This transducer measures the oil pressure in the oil discharge piping Standard for 19XR2~E/V/D and 19XR6/7
 This transducer measures the Oil pressure in the oil sump Standard for 19XR2~E/V/D and 19XR6/7
 This transducer measures the pressure of pump output  Standard for 19DV
 This transducer measures the pressure of bearing outlet Standard for 19DV
 This transducer measures the pressure of bearing inlet  Standard for 19DV
 This transducer measures the pressure of pump input  Standard for 19DV
This optional transducer measures the evaporator pressure dierence 
between entering and leaving water.
Optional for 19XR2~E/V/D, 19XR6/7 and 19DV
This optional transducer measures the condenser pressure dierence 
between entering and leaving water.
Optional for 19XR2~E/V/D, 19XR6/7 and 19DV
This is an option transducer, and it measures the pressure of evaporator 
entering water
Optional for 19XR2~E/V/D, 19XR6/7 and 19DV 
This is an optional transducer, and it measures the pressure of 
evaporator leaving water
Optional for 19XR2~E/V/D, 19XR6/7 and 19DV 
This is an optional transducer, and it measures the pressure of 
condenser entering water
Optional for 19XR2~E/V/D, 19XR6/7 and 19DV 
This is an optional transducer, and it measures the pressure of 
condenser leaving water
Optional for 19XR2~E/V/D, 19XR6/7 and 19DV 
Temperature sensors:
The system uses electronic sensors to measure and control the temperatures in the unit.
There are three types of temperature sensors, 5K thermistor, 10K thermistor and RTD (three wirings, MINCO S100308) 
based on the IOB channel congurations. 
  
 measures the temperature of entering evaporator water. Standard for 19XR2~E/V/D, 19XR6/7 and 19DV 
 measures the temperature of leaving evaporator water. Standard for 19XR2~E/V/D, 19XR6/7 and 19DV 
measures the temperature of entering condenser water. Standard for 19XR2~E/V/D, 19XR6/7 and 19DV 
measures the temperature of leaving condenser water.  Standard for 19XR2~E/V/D, 19XR6/7 and 19DV 
 measures the temperature of evaporator refrigerant liquid. Standard for 19XR2~E/V/D, 19XR6/7 and 19DV 
 measures the Compressor discharge temperature. Standard for 19XR2~E/V/D, 19XR6/7 and 19DV 
measure the low speed motor end bearing temperature Standard for 19XR6/7
measure the low speed compressor end bearing temperature Standard for 19XR6/7
measure the high speed motor end bearing temperature Standard for 19XR6/7
measure the high speed compressor end bearing temperature Standard for 19XR6/7
 Measure the compressor thrust bearing oil temperature Standard for 19XR2~E/V/D
 Measure the 1st stage bearing temperature Standard for 19DV
 Measure the 2nd stage bearing temperature Standard for 19DV
 Measure the bearing ref supply temperature Standard for 1-9DV
 The 3 sensors measure the temperature of  compressor motor windings  Standard for 19XR2~E/V/D, 19XR6/7 and 19DV
19XR2~E/V/D and 19DV only has 1 sensor.
 measures the compressor sump temperature of oil Standard for 19XR2~E/V/D and 19XR6/7
 measures the oil temperature in the oil discharge piping Standard for 19XR2~E/V/D and 19XR6/7
The temperature sensor range is -40 ~ +245°F.