30
Example: 
ECW sensor raw temp reads 32.6 °F
ECW temperature offset must be congured to -0.6 ^F (32–
32.6 = -0.6)
•  Step 3: Congure the sensor offset 
In temperature calibration screen, set the corresponding 
sensor temperature offset calculated in step 2. 
Note, the offset cannot exceed +/- 2 ^F. 
Example:
ECW temperature offset must be congured to -0.6 ^F (32-
32.6= -0.6)
•  Step 4: (optional) Verify that the sensor offset is 
congured correctly
Verify the following:
 - Sensor raw temp has not changed.
 - Sensor temperature offset now shows the congured 
value.
 - Sensor control value is calibrated, and now shows 32 °F.
Example:
“ECW sensor raw temp” still reads 32.6 °F
“ECW temperature offset” now shows -0.6 ^F
“Entering Chilled Water” now shows 32 °F.
5.28.1 - ISM Calibration on J8B 4-20mA Output
•  Step 1: Input a test output mA value on the touchscreen 
UI
The controller will make ISM output this mA value.
•  Step 2: Input the actual reading of mA value from VFD 
or mA meter
•  Step 3: Recalculate calibration factor
Calibration Factor = 1000 * (Actual Reading mA - 
output mA)
Range: 0-2000.
5.28.2 - ISM Calibration on J6 0-10v Input
•  Step 1: When chiller is running, record the VFD feedback 
voltage and the actual reading on ISM.
•  Step 2: Shut down the chiller, enable ISM Calibration
•  Step 3: Input the VFD feedback voltage
•  Step 4: Input the actual reading of ISM
•  Step 5: Recalculate calibration factor
Calibration Factor = 1000 * (VFD feedback voltage / ISM 
actual reading voltage)
Range: 800-1200
The purpose of the alarm email is to send e-mails to service 
for remote maintenance. 
A service configuration table EMAILCFG is used for 
network properties conguration. Once the EMAILCFG 
table conguration is changed, a test email will be sent for 
checking conguration. 
This task is checking the status of alarms. Once there is any 
alarm switches on, it would send the email with relative 
information. When all alarms go back to normal, an e-mail 
would be sent too.
The e-mail provides the unit description and location stored 
in the CTRL_ID table.
This  prognostic function is designed for service trouble 
shooting, can be access from Alarm Menu. The prognostic 
function enables the service engineer to resolve the problem 
before they affected the operating efciency and the chiller 
bottom life.
The following functions could be active only if the prognostic 
function is enabled (prog_en=YES)
The following screen is designed for prognostic. For each 
items, there are three different colors of trafc lamps to 
indicate the status. Green lamp indicate it is normal, red 
indicate there is problem and yellow lamp indicate it is near 
the problem region.