General Parameters General parameters GENUNIT
Temperatures Temperatures TEMP
Pressures Pressures PRESSURE
Inputs Status Inputs status INPUTS
Outputs Status Outputs status OUTPUTS
Hydraulic Status Hydraulic status HYDRLIC
Run Times Run times RUNTIME
Modes Modes MODES
Setpoint Table Setpoint table SETPOINT
Conguration Menu Conguration menu CONFIG
Quick Test Table Quick test table QCK_TEST
Maintenance Menu Maintenance menu MAINTAIN
Trending Trending TRENDING
* Depends on the selected language (English by default).
   
GENCONF 10H 1 //MAINMENU/CONFIG/
       
1 use_pass 1 to 9999 1111 - User Password 1 9999
2 min_o 1 to 15 2 min Stop to Start Delay 1 15
3 strt_dly 4 to 45 15 min Start to Start Delay 4 45
4 dem_sel 0 to 1 0 - Demand Limit Type 0 1
5 - Base Demand=0, 4-20mA=1
6 rampslct 0 to 1 1 - Pulldown Ramp Type 0 1
7 - Temp=0, Load=1
8 DEM_SLCT 0 to 1 0 - Demand Limit Source 0 1
9 - Amps=0, KW=1
   
RESETCFG 10H 4 //MAINMENU/CONFIG/
       
1 res_sel 0 to 3 0 - Temp Reset Type 0 3
2 - No=0, 4-20mA=1
3 - Remote Temp=2,Water DT=3
4 der_20ma -30.0 to 30.0 10 ^F Degrees Reset at 20mA -30 30
5 deg_rset -30.0 to 30.0 10 ^F Maximum Deg Temp Reset -30 30
6 remtm_fu -40.0 to 245.0 65 °F Remote Temp Full Reset -40 245
7 remtm_no -40.0 to 245.0 85 °F Remote Temp No Reset -40 245
8 drwdt_fu -30.0 to 30.0 10 ^F Deg Reset Water DT Full -30 30
9 ctldt_fu 0.0 to 15.0 0 ^F Controlled DT Full Reset 0 15
10 ctldt_no 0.0 to 15.0 10 ^F Controlled DT No Reset 0 15
   
GENUNIT 11H 1 //MAINMENU/
     








1 ctl_mode 0 to 3 - Control Mode 0 3
2 - Local=0, Network=1
3 - Remote=2, Local Sched=3
4 cm_stas1 - 1 Compressor1 Run Status
5 statstop stop/start - Deter Start Stop Command