78
CONNECT 13H 16 //MAINMENU/CONFIG/
17 - BACnet Conguration
18 bacena 0 to 1 0 - BACnet/IP Enable 0 1
19 bacunit 0 to 1 0 - BACnet Metric Unit 0 1
20 network 1 to 9999 1600 - BACnet Network 1 9999
21 bac_id 0 to 9999999 1600001 - BACnet Identier 0 9999999
22 auid 0 to 1 0 - ALC Auto Id Scheme 0 1
23 balmena 0 to 1 0 - BACnet Alarms Enable 0 1
24 bacschen 0 to 1 0 - BACnet Schedule Enable 0 1
25 mstpaddr 1 to 127 1 - MS/TP Mac address 1 127
26 mstpbaud 0 to 5 2 - MS/TP Baud rate 0 5
27 - 9600 = 0, 19200 = 1
28 - 38400 = 2, 57600 = 3
29 - 76800 = 4, 115200 = 5
30 maxmastr 1 to 127 3 - MS/TP Max Master 1 127
31 maxinfof 1 to 255 5 - MS/TP Max Info Frames 1 255
32 - Call Home Conguration
33 ch_opt 0 to 1 0 - Call Home Option 0 1
34 ch_ip_P1 0 to 255 140 - Call Home IP Addr Part 1 0 255
35 ch_ip_P2 0 to 255 206 - Call Home IP Addr Part 2 0 255
36 ch_ip_P3 0 to 255 129 - Call Home IP Addr Part 3 0 255
37 ch_ip_P4 0 to 255 10 - Call Home IP Addr Part 4 0 255
SETPOINT 17H 1 //MAINMENU/SETPOINT
1 ecw_sp 15.0 to 120.0 60 °F Cooling ECW Setpoint 15 120
2 lcw_sp 10.0 to 120.0 45 °F Cooling LCW Setpoint 10 120
3 ecdw_sp 63.0 to 150.0 104 °F Heating ECDW Setpoint 63 150
4 lcdw_sp 68.0 to 150.0 113 °F Heating LCDW Setpoint 68 150
5 ice_sp 15.0 to 60.0 40 °F Ice Build Setpoint 15 60
6 dem_base 10.0 to 100.0 100 % Base Demand Limit 10 100
7 EWT_OPT 0 to 1 0 - EWT Control Option 0 1
MAINMENU A001H 2
1 GENUNIT 0x0011_i1 ALL NONE NONE General Parameters
2 TEMP 0x0011_i2 ALL NONE NONE Temperatures
3 PRESSURE 0x0011_i3 ALL NONE NONE Pressures
4 INPUTS 0x0011_i4 ALL NONE NONE Inputs Status
5 OUTPUTS 0x0011_i5 ALL NONE NONE Outputs Status
6 HYDRLIC 0x0011_i6 ALL NONE NONE Hydraulic Status
7 RUNTIME 0x0011_i7 ALL NONE NONE Run Times
8 MODES 0x0011_i8 ALL NONE NONE Modes
9 SETPOINT 0x0017_i1 USER NONE NONE Setpoint
10 CONFIG 0xA001_i4 USER NONE NONE Conguration Menu