9
   
Damper Valve 
Feedback Fully Close
DI2 IOB2
High Pressure Switch DI3 IOB2
Ice Build Contact DI4 IOB2 User option, dry contact
Oil Heater Relay DO1 IOB2
Oil Pump Relay DO2 IOB2
Economizer Damper 
Valve Open
DO3 IOB2
Economizer Damper 
Valve Close
DO4 IOB2
Low Speed ME Brg 
Temp
AI1 IOB3
Low Speed CE Brg 
Temp
AI2 IOB3
High Speed ME Brg 
Temp
AI3 IOB3
High Speed CE Brg 
Temp
AI4 IOB3
Remote Reset Sensor AI5 IOB3 User option, 5K thermistor
Guide Vane 1 Actual 
Pos
AI6 IOB3
Common CHWS 
Temp
AI7 IOB3 Used for lead lag option
Auto Water Temp 
Reset
AI8 IOB3 User option, 4~20mA
Common CHWR 
Temp
AI9 IOB3 Used for lead lag option
Head Pressure 
Output
AO1 IOB3 Factory option
EC Valve Feedback 
Fully Open
DI1 IOB3 Factory option
EC Valve Feedback 
Fully Close
DI2 IOB3 Factory option
Spare Safety DI3 IOB3 User option, dry contact, 
normal open 
Power Request 
Feedback
DI4 IOB3 Marine option
EC Valve Solenoid / 
Open
DO1 IOB3 Factory option
EC Valve Close DO2 IOB3 Factory option
Free Cooling Mode DO3 IOB3 Factory option
Power Request 
Output
DO4 IOB3 Marine option
Entering Evap Water 
Pressure
AI3 IOB4 User option, if IOB4 
installed, same as follows
Leaving Evap Water 
Pressure
AI4 IOB4 User option
Entering Cond Water 
Pressure
AI5 IOB4 User option
Leaving Cond Water 
Pressure
AI6 IOB4 User option
Evap Water Flow 
Measurement
AI8 IOB4 User option, 4~20mA
Cond Water Flow 
Measurement
AI9 IOB4 User option, 4~20mA
Chilled Water Pump 
(Variable)
AO1 IOB4 User option, 4~20mA/0~5V
Condenser Water 
Pump (Variable)
AO2 IOB4 User option, 4~20mA/0~5V
Tower Fan (Variable) AO3 IOB4 User option, 4~20mA/0~5V
Customer Alert DI3 IOB4 Marine option, dry contact
Free Cooling Start 
Switch
DI4 IOB4 Marine option, dry contact
Chilled Water Pump DO1 IOB4 User option
Condenser Water 
Pump
DO2 IOB4 User option
Tower Fan High DO3 IOB4 User option
Tower Fan Low DO4 IOB4 User option
19XR2~E/V/D I/O, 19XRC mapping:
   
Entering Chilled 
Water Temperature
AI1 IOB1
Leaving Chilled Water 
Temperature
AI2 IOB1
Entering Condenser 
Water Temperature
AI3 IOB1
Leaving Condenser 
Water Temperature
AI4 IOB1
Evap. Refrigerant 
Liquid Temperature
AI5 IOB1
Comp Discharge 
Temperature
AI6 IOB1
Condenser Pressure AI7 IOB1
Evaporator Pressure AI8 IOB1
FS VFD Load Current AI10 IOB1 For free standing VFD
Variable Speed Oil 
Pump
AO1 IOB1 Factory option
Oil EXV Output AO2 IOB1 Factory option, 4~20mA
EC Valve Output mA AO3 IOB1 Factory option, 4~20mA
Chiller Lockout Input DI1 IOB1 User option, dry contact, 
normal open
Spare Safety DI2 IOB1 User option, dry contact, 
normal open
Remote Contact Input DI3 IOB1 User option, dry contact, 
“Closed” indicates Turn ON 
the chiller
Remote Emergency 
Stop Input
DI4 IOB1 User option, dry contact, 
“Closed” indicates chiller 
emergency stop 
Stage 1 IGV Increase DO1 IOB1
Stage 1 IGV 
Decrease
DO2 IOB1
Chiller Alarm Relay DO3 IOB1 User option, 24VAC output, 
recommend with external 
power supply
Motor Winding 
Temperature 1
AI1 IOB2
Thrust Bearing Oil 
Temperature
AI2 IOB2
Oil Sump 
Temperature
AI3 IOB2
Oil Supply 
Temperature
AI4 IOB2 Factory option
Guide Vane 1 Actual 
Pos
AI5 IOB2
Oil Supply Pressure AI6 IOB2
Oil Sump Pressure AI7 IOB2
EC Valve Feedback AI8 IOB2 Factory option, 4~20mA
Motor Winding 
Temperature 2
AI9 IOB2 For high voltage motor
Motor Winding 
Temperature 3
AI10 IOB2 For high voltage motor
Diuser Pressure AI11 IOB2 Factory option
Guide Vane1 Output AO1 IOB2 Factory option, for 4~20mA 
type guide vane
Diuser Output AO2 IOB2 Factory option
Evap Water Flow 
Switch
DI1 IOB2 User option, dry contact, 
“Closed” indicates “FLOW”
Cond Water Flow 
Switch
DI2 IOB2 User option, dry contact, 
“Closed” indicates “FLOW”
Ice Build Contact DI4 IOB2 User option, dry contact
Oil Heater Relay DO1 IOB2
Oil Pump Relay DO2 IOB2
EC Valve Soleniod / 
Open
DO3 IOB2 Factory option
Vapor Source SV DO4 IOB2 Factory option, for 19XRC
Heat Reclaim 
Entering Temp
AI3 IOB3 Heat reclaim option
Heat Reclaim Leaving 
Temp
AI4 IOB3 Heat reclaim option
Remote Reset Sensor AI5 IOB3 User option, 5K thermistor