The Main menu provides access to the main control parameters,
including general parameters, inputs and outputs status, etc.
To access the menu, press the Main menu button located in
the upper-left part of the Home screen.
Specic unit parameters can be accessed by pressing the icon 
corresponding to the desired category.
NOTE: The Trendings menu is displayed in form of a graph.
For more information about Trendings, see section 6.26.
CAUTION: Since specic units may not include additional
features, some tables may contain parameters that cannot
be congured for a given unit.
General parameters – GENUNIT
Name Status Unit
Displayed text* Description
CTRL_TYP 0 to 2 Local=0 Net.=1 Remote=2
Operating mode:
0 = Local
1 = Network
2 = Remote
STATUS Run Status
Unit running status: Off, Stopping, Delay, Running, Ready,
Override, Tripout, Test, Runtest
CHIL_S_S disable/enable Net.: Cmd Start/Stop
Unit start/stop via Network: When the unit is in Network mode,
start/stop command can be forced
CHIL_OCC no/yes Net.: Cmd Occupied
Unit time schedule via Network: When the unit is in Network mode,
the forced value can be used instead of the real occupancy state
min_left - min Minutes Left for Start Minutes before the unit start-up
HEATCOOL Heat/Cool status Heating/cooling status
HC_SEL 0 to 2 Heat/Cool Select Heating/cooling selection
0=Cool. 1=Heat. 2=Auto
0 = Cooling
1 = Heating
2 = Automatic heating/cooling control
SP_SEL 0 to 2 Setpoint Select Setpoint selection
0=Auto. 1=Spt1. 2=Spt2
0 = Automatic setpoint selection
1 = Setpoint 1 (active during occupied period)
2 = Setpoint 2 (active during unoccupied period)
SP_OCC no/yes Setpoint Occupied?
Setpoint status:
0 (no) = Unoccupied
1 (yes) = Occupied
CAP_T Unit Total Capacity Total unit capacity
CAPA_T Cir A Total Capacity Total capacity, circuit A
CAPB_T Cir B Total Capacity Total capacity, circuit B
SP Current setpoint Current setpoint
CTRL_PNT
-20 to 67
-4 to 153
°C
°F
Control Point Control point: Water temperature that the unit must produce
CTRL_WT
-20 to 67
-4 to 153
°C
°F
Control Water Temp Controlled water temperature
OAT - °C / °F Outdoor Air Temp Outdoor air temperature
EMSTOP disable/enable Emergency Stop
Emergency stop: Used to stop the unit regardless of its active
operating type
DEM_LIM 0 to 100 % Active Demand Limit Val
Active demand limit value: When the unit is Network mode, the
minimum value will be used compared to the status of the external
limit switch contact and the demand limit switch setpoint
LAG_LIM 0 to 100 % Lag Capacity Limit Value
Lag capacity limit value: Value that is forced by the master chiller
(master/slave assembly)
* Depends on the selected language (English by default)
Temperatures – TEMP
Name Status Unit Displayed text* Description
EWT - °C / °F Entering Fluid Temp Evaporator entering water temperature: Used for capacity control
LWT - °C / °F Leaving Fluid Temp Evaporator leaving water temperature: Used for capacity control
OAT - °C / °F Outdoor Air Temp
Outdoor air temperature: Used to determine a number of control
mechanisms such as heat/cool changeover, water exchanger
heater operation, defrost cycle, free cooling option, and more
SCT_A - °C / °F Saturated Cond Tmp cir A Saturated condensing temperature, circuit A
SST_A - °C / °F Saturated Suction Temp A Saturated suction temperature, circuit A
SUCT_A - °C / °F Compressor Suction Tmp A Compressor suction temperature, circuit A
SH_A - ^C / ^F Suction Superheat Tmp A Suction superheat temperature, circuit A
DEFRT_A - °C / °F Defrost Temperature A Defrost temperature, circuit A (heat pumps)
SCT_B - °C / °F Saturated Cond Tmp cir B Saturated condensing temperature, circuit B
5 - SMARTVIEW CONTROL: MENU STRUCTURE