Temperatures – TEMP (continued)
Name Status Unit Displayed text* Description
SST_B - °C / °F Saturated Suction Temp B Saturated suction temperature, circuit B
SUCT_B - °C / °F Compressor Suction Tmp B Compressor suction temperature, circuit B
SH_B - ^C / ^F Suction Superheat Tmp B Suction superheat temperature, circuit B
DEFRT_B - °C / °F Defrost Temperature B Defrost temperature, circuit B (heat pumps)
SPACETMP - °C / °F Optional Space Temp
Space (room) temperature: Applies to units with Energy
Management Module
CHWSTEMP - °C / °F Cold Water System Temp Cold water system temperature
*Depends on the selected language (English by default).
Pressures – PRESSURE
Name Status Unit Displayed text* Description
DP_A - kPa / PSI Discharge Pressure A Compressor discharge pressure, circuit A
SP_A - kPa / PSI Main Suction Pressure A Compressor suction pressure, circuit A
DP_B - kPa / PSI Discharge Pressure B Compressor discharge pressure, circuit B
SP_B - kPa / PSI Main Suction Pressure B Compressor suction pressure, circuit B
PUMP_EWP - kPa / PSI Inlet unit water press. Pump entering water pressure
PUMP_LWP - kPa / PSI Outlet unit water pres. Pump leaving water pressure
*Depends on the selected language (English by default).
Inputs – INPUTS
Name Status Unit Displayed text* Description
ONOFF_SW open/close - Remote On/Off Switch Remote on/off switch
HC_SW open/close - Remote HeatCool Switch Remote heating/cooling selection switch
SETP_SW open/close - Remote Setpoint Switch Remote setpoint selection switch
LIM_SW1 open/close - Limit Switch 1 Demand limit switch 1
LIM_SW2 open/close - Limit Switch 2 Demand limit switch 2 (EMM option)
LOCK_SW open/close - Customer Interlock
Customer interlock: When the contact is closed, the unit will be
stopped with no delay. The switch is provided on the customer's
terminal block of the optional EMM.
FLOW_SW open/close - Flow Switch Status Flow switch status
DSHTR_SW open/close - Desuper heater demand Desuperheater status
REM_LOCK open/close - Remote Interlock Status Remote interlock status
REVPH_SW open/close - Reverse Phase Detection Reverse phase detection
cp_a1_f open/close - Compressor A1 failure Compressor A1 failure
cp_a2_f open/close - Compressor A2 failure Compressor A2 failure
cp_a3_f open/close - Compressor A3 failure Compressor A3 failure
cp_a4_f open/close - Compressor A4 failure Compressor A4 failure
HP_SW_A open/close - High Pressure Switch A High pressure switch, circuit A
LEAK_A 0 to 10 V Leakage Detector Val A Leakage detector value, circuit A
cp_b1_f open/close - Compressor B1 failure Compressor B1 failure
cp_b2_f open/close - Compressor B2 failure Compressor B2 failure
cp_b3_f open/close - Compressor B3 failure Compressor B3 failure
cp_b4_f open/close - Compressor B4 failure Compressor B4 failure
HP_SW_B open/close - High Pressure Switch B High pressure switch, circuit B
LEAK_B 0 to 10 V Leakage Detector Val B Leakage detector value, circuit B
*Depends on the selected language (English by default).
5 - SMARTVIEW CONTROL: MENU STRUCTURE