Carrier SmartView - Output Commands List

Carrier SmartView
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Outputs – OUTPUTS
Name Status Unit Displayed text* Description
CP_A1 off/on - Compressor A1 Compressor A1 command
CP_A2 off/on - Compressor A2 Compressor A2 command
CP_A3 off/on - Compressor A3 Compressor A3 command
CP_A4 off/on - Compressor A4 Compressor A4 command
FAN_A1_0 off/on - Fan A1 Low Speed Fan A1 low speed (optional)
FAN_A1_1 off/on - Fan A1 High Speed Fan A1 command
FAN_A2 off/on - Fan A2 Fan A2 command
FAN_A3 off/on - Fan A3 Fan A3 command
FAN_A4 off/on - Fan A4 Fan A4 command
FAN_ST_A 0 to 6 - Fan Staging Number Cir A Current fan stage of circuit A
VARFAN_A Variable fan A command Variable fan A command
EXV_A 0 to 100 % EXV position Circuit A EXV position, circuit A
REV_A off/on - 4-way Refrig. Valve A
4-way refrigerant valve, circuit A: Used to manage cooling/heating/
defrost operation (heat pumps)
HD_HTR_A off/on - Compressor Head Heater A Compressor head heater, circuit A: Applies only to 30RQP units
CP_B1 off/on - Compressor B1 Compressor B1 command
CP_B2 off/on - Compressor B2 Compressor B2 command
CP_B3 off/on - Compressor B3 Compressor B3 command
CP_B4 off/on - Compressor B4 Compressor B4 command
FAN_B1_0 off/on - Fan B1 Low Speed Fan B1 low speed (optional)
FAN_B1_1 off/on - Fan B1 High Speed Fan B1 command
FAN_B2 off/on - Fan B2 Fan B2 status
FAN_B3 off/on - Fan B3 Fan B3 status
FAN_B4 off/on - Fan B4 Fan B4 status
FAN_ST_B 0 to 6 - Fan Staging Number Cir B Current fan stage of circuit B
VARFAN_B Variable fan B command Variable fan B command
EXV_B 0 to 100 % EXV position Circuit B EXV position, circuit B
REV_B off/on - 4-way Refrig. Valve B
4-way refrigerant valve, circuit B: Used to manage cooling/heating/
defrost operation (heat pumps)
ALARM off/on - Alarm Relay Status Alarm relay status
HD_HTR_B off/on - Compressor Head Heater B Compressor head heater, circuit B: Applies only to 30RQP units
RUNNING off/on - Running Relay Status Running relay status
ALERT off/on - Alert Relay State Alert relay state
SHUTDOWN off/on - Shutdown Indicator State Shutdown indicator state
EXCH_HTR off/on - Exchanger heater Evaporator heater
SET_FLOW off/on - Flow Switch Setpoint cfg Flow switch setpoint conguration
*Depends on the selected language (English by default).
Pump Status – PUMPSTAT
Name Status Unit Displayed text* Description
ROTWPUMP no/yes - Rotate Water Pumps Now? Water pumps rotation
WPUMP_1 off/on - Water Pump #1 Command Water pump 1 control
WPUMP_2 off/on - Water Pump #2 Command Water pump 2 control
wp_out - kPa / PSI Outlet Water Pres.(cor)
Outlet water pressure (corrected by temperature):
Applies to units with the hydronic kit option
wp_in - kPa / PSI Inlet Water Pres.(cor)
Inlet water pressure (corrected by temperature):
Applies to units with the hydronic kit option
WP_CAL no/yes - Water Pres. Calibration? Water pressure calibration
wp_off - kPa / PSI Water Pressure Offset Water pressure offset
wp_lt - kPa / PSI Delta Pressure Filter Delta pressure lter
wp_min - kPa / PSI Minimum Water Pressure Minimum water pressure
ow - l/s / GPS Water Flow Water ow rate
dt_stp - ^C / ^F Water Delta T Setpoint Water delta temperature setpoint
delta_t - ^C / ^F Current Water Delta T Current water delta temperature
dp_stp - kPa / PSI Water Delta P Setpoint Water delta pressure setpoint
delta_p - kPa / PSI Current Water Delta P Current water delta pressure
DRV_OUT 0 to 100 % Drive Output Drive output
*Depends on the selected language (English by default).
5 - SMARTVIEW CONTROL: MENU STRUCTURE