Outputs – OUTPUTS
Name Status Unit Displayed text* Description
CP_A1 off/on - Compressor A1 Compressor A1 command
CP_A2 off/on - Compressor A2 Compressor A2 command
CP_A3 off/on - Compressor A3 Compressor A3 command
CP_A4 off/on - Compressor A4 Compressor A4 command
FAN_A1_0 off/on - Fan A1 Low Speed Fan A1 low speed (optional)
FAN_A1_1 off/on - Fan A1 High Speed Fan A1 command
FAN_A2 off/on - Fan A2 Fan A2 command
FAN_A3 off/on - Fan A3 Fan A3 command
FAN_A4 off/on - Fan A4 Fan A4 command
FAN_ST_A 0 to 6 - Fan Staging Number Cir A Current fan stage of circuit A
VARFAN_A Variable fan A command Variable fan A command
EXV_A 0 to 100 % EXV position Circuit A EXV position, circuit A
REV_A off/on - 4-way Refrig. Valve A
4-way refrigerant valve, circuit A: Used to manage cooling/heating/
defrost operation (heat pumps)
HD_HTR_A off/on - Compressor Head Heater A Compressor head heater, circuit A: Applies only to 30RQP units
CP_B1 off/on - Compressor B1 Compressor B1 command
CP_B2 off/on - Compressor B2 Compressor B2 command
CP_B3 off/on - Compressor B3 Compressor B3 command
CP_B4 off/on - Compressor B4 Compressor B4 command
FAN_B1_0 off/on - Fan B1 Low Speed Fan B1 low speed (optional)
FAN_B1_1 off/on - Fan B1 High Speed Fan B1 command
FAN_B2 off/on - Fan B2 Fan B2 status
FAN_B3 off/on - Fan B3 Fan B3 status
FAN_B4 off/on - Fan B4 Fan B4 status
FAN_ST_B 0 to 6 - Fan Staging Number Cir B Current fan stage of circuit B
VARFAN_B Variable fan B command Variable fan B command
EXV_B 0 to 100 % EXV position Circuit B EXV position, circuit B
REV_B off/on - 4-way Refrig. Valve B
4-way refrigerant valve, circuit B: Used to manage cooling/heating/
defrost operation (heat pumps)
ALARM off/on - Alarm Relay Status Alarm relay status
HD_HTR_B off/on - Compressor Head Heater B Compressor head heater, circuit B: Applies only to 30RQP units
RUNNING off/on - Running Relay Status Running relay status
ALERT off/on - Alert Relay State Alert relay state
SHUTDOWN off/on - Shutdown Indicator State Shutdown indicator state
EXCH_HTR off/on - Exchanger heater Evaporator heater
SET_FLOW off/on - Flow Switch Setpoint cfg Flow switch setpoint conguration
*Depends on the selected language (English by default).
Pump Status – PUMPSTAT
Name Status Unit Displayed text* Description
ROTWPUMP no/yes - Rotate Water Pumps Now? Water pumps rotation
WPUMP_1 off/on - Water Pump #1 Command Water pump 1 control
WPUMP_2 off/on - Water Pump #2 Command Water pump 2 control
wp_out - kPa / PSI Outlet Water Pres.(cor)
Outlet water pressure (corrected by temperature):
Applies to units with the hydronic kit option
wp_in - kPa / PSI Inlet Water Pres.(cor)
Inlet water pressure (corrected by temperature):
Applies to units with the hydronic kit option
WP_CAL no/yes - Water Pres. Calibration? Water pressure calibration
wp_off - kPa / PSI Water Pressure Offset Water pressure offset
wp_lt - kPa / PSI Delta Pressure Filter Delta pressure lter
wp_min - kPa / PSI Minimum Water Pressure Minimum water pressure
ow - l/s / GPS Water Flow Water ow rate
dt_stp - ^C / ^F Water Delta T Setpoint Water delta temperature setpoint
delta_t - ^C / ^F Current Water Delta T Current water delta temperature
dp_stp - kPa / PSI Water Delta P Setpoint Water delta pressure setpoint
delta_p - kPa / PSI Current Water Delta P Current water delta pressure
DRV_OUT 0 to 100 % Drive Output Drive output