Run Times – RUNTIME
Name Status Unit Displayed text* Description
hr_mach  - hour Machine Operating Hours Unit operating hours
st_mach  - - Machine Starts Number Number of unit starts
hr_cp_a1  - hour Compressor A1 Hours Operating hours, compressor A1
hr_cp_a2  - hour Compressor A2 Hours Operating hours, compressor A2
hr_cp_a3  - hour Compressor A3 Hours Operating hours, compressor A3
hr_cp_a4  - hour Compressor A4 Hours Operating hours, compressor A4
hr_cp_b1  - hour Compressor B1 Hours Operating hours, compressor B1
hr_cp_b2  - hour Compressor B2 Hours Operating hours, compressor B2
hr_cp_b3  - hour Compressor B3 Hours Operating hours, compressor B3
hr_cp_b4  - hour Compressor B4 Hours Operating hours, compressor B4
st_cp_a1  - - Compressor A1 Starts Number of starts, compressor A1
st_cp_a2  - - Compressor A2 Starts Number of starts, compressor A2
st_cp_a3  - - Compressor A3 Starts Number of starts, compressor A3
st_cp_a4  - - Compressor A4 Starts Number of starts, compressor A4
st_cp_b1  - - Compressor B1 Starts Number of starts, compressor B1
st_cp_b2  - - Compressor B2 Starts Number of starts, compressor B2
st_cp_b3  - - Compressor B3 Starts Number of starts, compressor B3
st_cp_b4  - - Compressor B4 Starts Number of starts, compressor B4
hr_fana1  - hour Fan A1 Hours Operating hours, fan A1
hr_fana2  - hour Fan A2 Hours Operating hours, fan A2
hr_fana3  - hour Fan A3 Hours Operating hours, fan A3
hr_fana4  - hour Fan A4 Hours Operating hours, fan A4
hr_fanb1  - hour Fan B1 Hours Operating hours, fan B1
hr_fanb2  - hour Fan B2 Hours Operating hours, fan B2
hr_fanb3  - hour Fan B3 Hours Operating hours, fan B3
hr_fanb4  - hour Fan B4 Hours Operating hours, fan B4
hr_pump1  - hour Water Pump #1 Hours Operating hours, water pump 1
hr_pump2  - hour Water Pump #2 Hours Operating hours, water pump 2
hr_hrpmp  - hour Reclaim Pump Hours Not available
hrfcpmpa  - hour Refrig. Pump Cir A Hours Not available
hrfcpmpb  - hour Refrig. Pump Cir B Hours Not available
nb_defra - - Circuit A Defrost Number Number of defrost sessions that occurred on circuit A
nb_defrb - - Circuit B Defrost Number Number of defrost sessions that occurred on circuit B
*Depends on the selected language (English by default).
  Modes – MODES
Name Status Unit Displayed text* Description
m_delay no/yes - Start Up Delay In Effect Start-up delay in effect
m_2stpt no/yes - Second Setpoint In Use
Second setpoint in use: The setpoint used during unoccupied 
periods
m_reset no/yes - Reset In Effect Setpoint reset active
m_demlim no/yes - Demand limit active Demand limit active
m_rpload no/yes - Ramp Loading Active Ramp loading active
m_whtr no/yes - Water Exchanger Heater Water exchanger heater active
m_pmprot no/yes - Water Pump Rotation Water pump rotation
m_pmpper no/yes - Pump Periodic Start Pump periodic start 
m_lowsca no/yes - Low Suction Circuit A Low suction, circuit A
m_lowscb no/yes - Low Suction Circuit B Low suction, circuit B
m_hidgta no/yes - High DGT Circuit A High DGT, circuit A
m_hidgtb no/yes - High DGT Circuit B High DGT, circuit B
m_hiprsa no/yes - High Press Override CirA High pressure override, circuit A
m_hiprsb no/yes - High Press Override CirB High pressure override, circuit B
m_lowsha no/yes - Superheat Override Cir A Superheat override, circuit A
m_lowshb no/yes - Superheat Override Cir B Superheat override, circuit B
m_dltp_a no/yes - Low Delta Press Cir A Low delta pressure, circuit A
m_dltp_b no/yes - Low Delta Press Cir B Low delta pressure, circuit B
5 - SMARTVIEW CONTROL: MENU STRUCTURE