Modes – MODES (continued)
Name Status Unit Displayed text* Description
m_night no/yes - Night Low Noise Active Night low noise active
m_hsm no/yes - System Manager Active System Manager active
m_slave no/yes - Master Slave Active Master/slave mode active
m_autoch no/yes - Auto Changeover Active Automatic changeover active
m_defr_a no/yes - Defrost Active Circuit A Defrost mode active, circuit A (heat pumps)
m_defr_b no/yes - Defrost Active Circuit B Defrost mode active, circuit B (heat pumps)
m_recl_a no/yes - Reclaim Active Circuit A Not available
m_recl_b no/yes - Reclaim Active Circuit B Not available
m_free_a no/yes - Free Cooling Active A Free cooling mode active, circuit A
m_free_b no/yes - Free Cooling Active B Free cooling mode active, circuit B
m_boiler no/yes - Boiler Active Boiler active
m_ehs no/yes - Electric Heater Active Electric heater active
m_ewtlck no/yes - Heating Low EWT Lockout Heating low EWT lockout
m_ice no/yes - Ice Mode In Effect Ice mode active
*Depends on the selected language (English by default).
Free Cooling Status – FREECOOL
Name Status Unit Displayed text* Description
FC_SW open/close - FreeCool Disable Switch
Free cooling disable switch. The contact is normally open (if the
switch is closed when the unit is in Remote mode, free cooling
cycle cannot be started)
FC_DSBLE no/yes no Free Cooling Disable ?
Free Cooling enable/disable option (if this parameter is set to “no”
when the unit is in Network mode, free cooling cycle cannot be
started)
fc_delta ^C / ^F Free Cooling Delta T Free cooling delta T
CIRCUIT A Circuit A
mc_pwr_a kW Mecha. Cooling Power A Mechanical cooling power (circuit A)
fc_pwr_a kW Free Cool Maxi Power A Max. free cooling power (circuit A)
fc_nxt_a min Next Session A In Next free cooling session allowed in (circuit A)
fc_tmr_a min FreeCool Timeout A Free cooling timeout (circuit A)
fc_ok_a no/yes - Free Cool Conditions A ? Free cooling conditions status (circuit A)
fc_on_a no/yes - Free Cooling Active A Free cooling active status (circuit A)
fc_ovr_a - Free Cooling Override A Free cooling override (circuit A)
fan_st_a - Fan Staging Number A Fan stage (circuit A)
fc_v_p_a % 3-Way Valve Position A 3-way valve position
fc_vlv_a 0 to 6 - 3-Way Valve Status A
3-way valve status: 0 = Stopped, 1 = Closed, 2 = Opening,
3 = Closing, 4 = Opened, 5/6 = Failed
fc_pmp_a off/on - Refrigerant Pump Out A Refrigerant pump output status (circuit A)
fcPmpS_a - Pump Status A Pump status (circuit A)
fc_oup_a kPa / PSI Pump Outlet Pressure A Pump outlet pressure (circuit A)
fc_inp_a kPa / PSI Pump Inlet Pressure A Pump inlet pressure (circuit A)
fc_dp_a kPa / PSI Pump Pressure Delta A Pump pressure delta (circuit A)
CIRCUIT B CIRCUIT B
mc_pwr_b kW Mecha. Cooling Power B Mechanical cooling power (circuit B)
fc_pwr_b kW Free Cool Maxi Power B Max. free cooling power (circuit B)
fc_nxt_b min Next Session B In Next free cooling session allowed in (circuit B)
fc_tmr_b min FreeCool Timeout B Free cooling timeout (circuit B)
fc_ok_b no/yes - Free Cool Conditions B ? Free cooling conditions status (circuit B)
fc_on_b no/yes - Free Cooling Active B Free cooling active status (circuit B)
fc_ovr_b - Free Cooling Override B Free cooling override (circuit B)
fan_st_b - Fan Staging Number B Fan stage (circuit B)
fc_v_p_b % 3-Way Valve Position B 3-way valve position
fc_vlv_b 0 to 6 - 3-Way Valve Status B
3-way valve status: 0 = Stopped, 1 = Closed, 2 = Opening,
3 = Closing, 4 = Opened, 5/6 = Failed
fc_pmp_b off/on - Refrigerant Pump Out B Refrigerant pump output status (circuit B)
fcPmpS_b - Pump Status B Pump status (circuit B)
fc_oup_b kPa / PSI Pump Outlet Pressure B Pump outlet pressure (circuit B)
fc_inp_b kPa / PSI Pump Inlet Pressure B Pump inlet pressure (circuit B)
5 - SMARTVIEW CONTROL: MENU STRUCTURE
18