Free Cooling Status – FREECOOL (continued)
Name Status Unit Displayed text* Description
fc_dp_b kPa / PSI Pump Pressure Delta B Pump pressure delta (circuit B)
*Depends on the selected language (English by default).
Energy Management – EMM_STAT
Name Status Unit Displayed text* Description
OCC_OVSW open/close - Occupied Override Switch Occupied override switch status
ICE_SW open/close - Ice Done Storage Switch Ice done storage switch status
SP_RESET 4 to 20 mA Setpoint Reset Signal Setpoint reset signal
LIM_4_20 4 to 20 mA Limit 4-20mA Signal Limit 4-20 mA signal
CAPT_010 - V Chiller Capacity Running
Chiller capacity running: 0 to 10 VDC signal
corresponding to 0-100% capacity
BOILER off/on - Boiler Output Boiler output
EHS1 off/on - Electrical Heat Stage 1 Electric heater stage 1 (heat pumps)
EHS2 off/on - Electrical Heat Stage 2 Electric heater stage 2 (heat pumps)
EHS3 off/on - Electrical Heat Stage 3 Electric heater stage 3 (heat pumps)
EHS4 off/on - Electrical Heat Stage 4 Electric heater stage 4 (heat pumps)
ALERT off/on - Alert Relay Status Alert relay status
DSH_PUMP off/on - Desuperheater Pump Desuperheater pump status
*Depends on the selected language (English by default).
DC Free Cooling Status – DCFC_STA
Name Status Unit Displayed text* Description
oat - °C / °F OAT Free Cooling Dry Cooler Free Cooling: OAT
lwt - °C / °F FC Leaving Water Temp Dry Cooler Free Cooling: Leaving water temperature
wloop - °C / °F FC Water Loop Temp Dry Cooler Free Cooling: Water loop temperature
m_dcfc no/yes - Free Cooling Mode Active Dry Cooler Free Cooling mode active
dcfc_cap 0 to 100 % FC Capacity Dry Cooler Free Cooling capacity
f_stage 0 to 20 - Fix Speed Fans Stage Dry Cooler Free Cooling: Fan stage (xed speed fans)
vf_speed 0 to 100 % Varifan Speed Dry Cooler Free Cooling: Fan speed (variable speed)
pid_out 0 to 100 % PID Output Status of PID output
FC_HOUR 0 to 999999 hour DCFC Operating Hours Dry Cooler Free Cooling: Operating hours
FC_FAN1S 0 to 999999 - DCFC Fan Stage 1 Start DCFC / Fan stage 1: Number of starts
FC_FAN1H 0 to 999999 hour DCFC Fan Stage 1 Hours DCFC / Fan stage 1: Operating hours
FC_FAN2S 0 to 999999 - DCFC Fan Stage 2 Start DCFC / Fan stage 2: Number of starts
FC_FAN2H 0 to 999999 hour DCFC Fan Stage 2 Hours DCFC / Fan stage 2: Operating hours
FC_FAN3S 0 to 999999 - DCFC Fan Stage 3 Start DCFC / Fan stage 3: Number of starts
FC_FAN3H 0 to 999999 hour DCFC Fan Stage 3 Hours DCFC / Fan stage 3: Operating hours
FC_FAN4S 0 to 999999 - DCFC Fan Stage 4 Start DCFC / Fan stage 4: Number of starts
FC_FAN4H 0 to 999999 hour DCFC Fan Stage 4 Hours DCFC / Fan stage 4: Operating hours
FC_FAN5S 0 to 999999 - DCFC Fan Stage 5 Start DCFC / Fan stage 5: Number of starts
FC_FAN5H 0 to 999999 hour DCFC Fan Stage 5 Hours DCFC / Fan stage 5: Operating hours
FC_FAN6S 0 to 999999 - DCFC Fan Stage 6 Start DCFC / Fan stage 6: Number of starts
FC_FAN6H 0 to 999999 hour DCFC Fan Stage 6 Hours DCFC / Fan stage 6: Operating hours
FC_FAN7S 0 to 999999 - DCFC Fan Stage 7 Start DCFC / Fan stage 7: Number of starts
FC_FAN7H 0 to 999999 hour DCFC Fan Stage 7 Hours DCFC / Fan stage 7: Operating hours
FC_VFANS 0 to 999999 - DCFC Variable Fan Start DCFC / Variable speed fan: Number of starts
FC_VFANH 0 to 999999 hour DCFC Variable Fan Hours DCFC / Variable speed fan: Operating hours
*Depends on the selected language (English by default).