Msc Status – MSC_STAT
Name Status Unit Displayed text* Description
m_ecopmp no/yes - Eco Pump Mode Active
Eco pump mode status: When this mode is active, the pump is
stopped periodically when the unit is in Standby
*Depends on the selected language (English by default).
Setpoint Conguration – SETPOINT
Name Status* Default Unit Displayed text** Description
csp1
-28.9 to 26 6.7 °C
Cooling Setpoint 1 Cooling setpoint 1
-20.0 to 78.8 44 °F
csp2
-28.9 to 26 6.7 °C
Cooling Setpoint 2 Cooling setpoint 2
-20.0 to 78.8 44 °F
ice_sp
-28.9 to 26 6.7 °C
Cooling Ice Setpoint Ice storage setpoint
-20.0 to 78.8 44 °F
cramp_sp
0.1 to 1.1 0.6 ^C
Cooling Ramp Loading Cooling ramp loading setpoint
0.2 to 2.0 1 ^F
hsp1
26.7 to 63 37.8 °C
Heating Setpoint 1 Heating setpoint 1
80.0 to 145.4 100 °F
hsp2
26.7 to 63 37.8 °C
Heating Setpoint 2 Heating setpoint 2
80.0 to 145.4 100 °F
hramp_sp
0.1 to 1.1 0.6 ^C
Heating Ramp Loading Heating ramp loading setpoint
0.2 to 2.0 1 ^F
cauto_sp
3.9 to 50 23.9 °C
Cool Changeover Setpt Cooling changeover setpoint
39.0 to 122.0 75 °F
hauto_sp
0 to 46.1 17.8 °C
Heat Changeover Setpt Heating changeover setpoint
32.0 to 115.0 64 °F
lim_sp1 0 to 100 100 % Switch Limit Setpoint 1 Switch limit setpoint 1
lim_sp2 0 to 100 100 % Switch Limit Setpoint 2 Switch limit setpoint 2
lim_sp3 0 to 100 100 % Switch Limit Setpoint 3 Switch limit setpoint 3
hr_stp
35 to 50 50 °C
Heat Reclaim Setpoint Not available
95 to 122 122 °F
hr_deadb
2.8 to 15 5 ^C
Heat Reclaim Deadband Not available
5 to 27 9 ^F
min_sct
23.9 to 50 40 °C
Desuperheat Min SCT Minimum SCT when desuperheater is enabled
75 to 122 104 °F
*Depends on the selected language (English by default).
**The range may vary depending on the unit conguration, e.g. uid type.
Trendings – TRENDING
Name Status Unit Displayed text* Description**
GENUNIT_CAPA_T 0 to 100 % Cir A Total Capacity Total capacity, circuit A
GENUNIT_CAPB_T 0 to 100 % Cir B Total Capacity Total capacity, circuit B
GENUNIT_CTRL_PN - °C / °F Control Point Control point
TEMP_OAT - °C / °F Outdoor Air Temp Outdoor air temperature
TEMP_EWT - °C / °F Cooler Entering Fluid Evaporator entering water temperature
TEMP_LWT - °C / °F Cooler Leaving Fluid Evaporator leaving water temperature
TEMP_SCT_A - °C / °F Saturated Cond Tmp cir A Saturated condensing temperature, circuit A
TEMP_SCT_B - °C / °F Saturated Cond Tmp cir B Saturated condensing temperature, circuit B
TEMP_SST_A - °C / °F Saturated Suction Temp A Saturated suction temperature, circuit A
TEMP_SST_B - °C / °F Saturated Suction Temp B Saturated suction temperature, circuit B
*Depends on the selected language (English by default).
**The list of trending points cannot be modied. Trending points can only be enabled or disabled.