The Conguration menu gives access to a number of us-
er-modiable parameters such as pump conguration, schedule
menu, etc. The Conguration menu is password-protected.
■ To access the Conguration menu, press the Main menu button
located in the upper-left part of the Home screen, and then
select Conguration Menu.
■ Once all the necessary modications have been made, press
the Save button to conrm your changes or the Cancel button
to exit the screen without making modications.
5 - SMARTVIEW CONTROL: MENU STRUCTURE
System conguration override: In some cases it is possible to
override system conguration. Note that not all parameters can
be overridden by the control.
CAUTION: Since specic units may not include additional
features, some tables may contain parameters that cannot
be congured for a given unit.
General Conguration – GEN_CONF
Name Status Default Unit Displayed text* Description
prio_cir 0 to 2 0 -
Cir Priority Sequence Circuit priority
0=Auto 0 = Automatic circuit selection
1=A Prio 1 = Circuit A priority
2=B Prio 2 = Circuit B priority
seq_typ no/yes no - Staged Loading Sequence Staged loading sequence
ramp_sel no/yes no - Ramp Loading Select Ramp loading selection
lim_sel 0 to 2 0 -
Demand Limit Type Select Demand limit selection
0 = None 0 = None
1 = Switch Control 1 = Switch control
2 = 4-20mA Control 2 = 4-20 mA control
off_on_d 1 to 15 1 min Unit Off to On Delay Unit Off to On delay
heat_th
-12 to 0 -12 °C
Heating OAT Threshold Heating OAT threshold
10.4 to 32.0 10.4 °F
nh_start - - - Night Mode Start Hour Night mode start hour
nh_end - - - Night Mode End Hour Night mode end hour
nh_limit 0 to 100 100 % Night Capacity Limit Night capacity limit
ice_cnfg no/yes no - Ice Mode Enable Ice mode enabled (EMM)
both_sel no/yes no - Both Command Sel (HSM) Both command selection (HSM)
auto_sel no/yes no - Auto Changeover Select Automatic changeover selection
*Depends on the selected language (English by default).
Pump Conguration – PUMPCONF
Name Status Default Unit Displayed text* Description
pump_seq 0 to 4 0 -
Pumps Sequence Pumps sequence
0 = No Pump 0 = No pump
1 = One Pump Only 1 = One pump only (units with one pump)
2 = Two Pumps Auto 2 = Two pumps automatic control
3 = Pump#1 Manual 3 = Pump 1 selected (units with two pumps)
4 = Pump#2 Manual 4 = Pump 2 selected (units with two pumps)
pump_del 24 to 3000 48 hour Pump Auto Rotation Delay Pump automatic rotation delay
pump_per no/yes no - Pump Sticking Protection Pump sticking protection
pump_sby no/yes no - Stop Pump During Standby Pump stop when the unit is in standby
pump_loc no/yes yes - Flow Checked If Pump Off Flow checked if pump is off
*Depends on the selected language (English by default).
23