Reset Conguration – RESETCFG
Name Status Default Unit Displayed text* Description
cr_sel 0 to 4 0 - Cooling Reset Select Cooling reset selection
hr_sel 0 to 4 0 - Heating Reset Select Heating reset selection
0=None, 1=OAT, 2=Delta T
3=4-20mA control
4=Space Temp
0 = None, 1 = OAT, 2 = Delta T
3 = 4-20 mA control
4 = Space temperature
Cooling Cooling
oat_crno
-10 to 51.7 -10 °C
OAT No Reset Value OAT, no reset value
14 to 125 14 °F
oat_crfu
-10 to 51.7 -10 °C
OAT Full Reset Value OAT, max. reset value
14 to 125 14 °F
dt_cr_no
0 to 13.9 0 ^C
Delta T No Reset Value Delta T, no reset value
0 to 25 0 ^F
dt_cr_fu
0 to 13.9 0 ^C
Delta T Full Reset Value Delta T, max. reset value
0 to 25 0 ^F
I_cr_no 0 to 20 0 mA Current No Reset Value Current, no reset value
I_cr_fu 0 to 20 0 mA Current Full Reset Value Current, max. reset value
spacr_no
-10 to 51.7 -10 °C
Space T No Reset Value Space temperature, no reset value
14 to 125 14 °F
spacr_fu
-10 to 51.7 -10 °C
Space T Full Reset Value Space temperature, max. reset value
14 to 125 14 °F
cr_deg
-16.7 to 16.7 0 ^C
Cooling Reset Deg. Value Maximum cooling reset value
-30 to 30 0 ^F
Heating Heating
oat_hrno
-10 to 51.7 -10 °C
OAT No Reset Value OAT, no reset value
14 to 125 14 °F
oat_hrfu
-10 to 51.7 -10 °C
OAT Full Reset Value OAT, max. reset value
14 to 125 14 °F
dt_hr_no
0 to 13.9 0 ^C
Delta T No Reset Value Delta T, no reset value
0 to 25 0 ^F
dt_hr_fu
0 to 13.9 0 ^C
Delta T Full Reset Value Delta T, max. reset value
0 to 25 0 ^F
I_hr_no 0 to 20 0 mA Current No Reset Value Current, no reset value
I_hr_fu 0 to 20 0 mA Current Full Reset Value Current, max. reset value
spahr_no
-10 to 51.7 -10 °C
Space T No Reset Value Space T, no reset value
14 to 125 14 °F
spahr_fu
-10 to 51.7 -10 °C
Space T Full Reset Value Space T, max. reset value
14 to 125 14 °F
hr_deg
-16.7 to 16.7 0 ^C
Heating Reset Deg. Value Maximum heating reset value
-30 to 30 0 ^F
*Depends on the selected language (English by default).
Backup Conguration – BACKUP
Name Status Default Unit Displayed text* Description
boil_th
-15 to 15 -10 °C
Boiler OAT Threshold Boiler OAT threshold
5 to 59 14 °F
ehs_th
-5 to 21 5 °C
Elec Stage OAT Threshold Electric heater stage OAT threshold
23 to 70 41 °F
ehs_pull 0 to 60 0 min Electrical Pulldown Time Electrical pulldown time
ehs_back no/yes no - Elec Stage 1 for backup Electric heater stage 1 (backup)
ehs_defr no/yes no - Quick EHS for defrost Quick EHS for defrost
ehs_kp -20 to 20 2 - EHS Proportional Gain EHS proportional gain
ehs_ki -5 to 5 0 - EHS Integral Gain EHS integral gain
ehs_kd -20 to 20 0 - EHS Derivative Gain EHS derivative gain
*Depends on the selected language (English by default).
5 - SMARTVIEW CONTROL: MENU STRUCTURE
24