Free Cooling Cong – FREECONF
Name Status Default Unit Displayed text* Description
free_th
-35 to 30
-31 to 86
0
32
°C
°F
OAT Threshold Free cooling OAT threshold
fcdeltat
5 to 10
9 to 18
8
14.4
^C
^F
Minimum Delta T
Minimum delta T (min difference between the control
point and OAT)
timeout 5 to 60 10 min Full Load Timeout Full load timeout
pre_cool no/yes no - Pre-Cooling Select Pre-cooling selection
*Depends on the selected language (English by default).
Date/Time Conguration – DATETIME
Status Displayed text* Description
on/off Daylight Saving Time Information of setting the clocks forward one hour from standard
time during the summer months, and back again in the fall, in order
to make better use of natural daylight
Greenwich Mean Time (UTC) Location Time zone
YYYY/MM/DD, HH:MM:SS Date/Time Current date and time (must be set manually)
no/yes Today is a Holiday Information about holidays (read-only). Please note that holidays
are set in the Holiday menu (see also section 5.4)
no/yes Tomorrow is a Holiday Information about the upcoming holiday period (read-only). Please
note that holidays are set in the Holiday menu (see also section 5.4)
*Depends on the selected language (English by default).
NOTE: The Date/Time Conguration menu appears also in the System menu (see also section 5.7).
Control Identication Menu – CTRL_ID
Status Default Displayed text* Description
0-239 1 CCN Element Number Element number
0-239 0 CCN Bus Number Bus number
9600 / 19200 / 38400 9600 CCN Baud Rate Communication speed
- 30RBM/30RBP
30RQM/30RQP
Device Description Unit description
- - Location Description Location description: The number corresponds to the country
- ECG-SR-20V4B100 Software Part Number Software version
- - Serial Number Serial number (MAC address)
*Depends on the selected language (English by default).
Add Options Menu – ADD_OPT
Displayed text* Description
MAC address Controller MAC address: This MAC address is requested by your Local Carrier service
representative when ordering any software-protected option (see also section 6.23)
Please Enter Your Software Activation Key: Type the Software Activation Key provided by your Local Carrier service representative
(see also section 6.23)
Unit must be OFF The unit should not be operating when installing the Software Activation Key
*Depends on the selected language (English by default).
NOTE: If you need to add an option, please contact your local carrier Service provider.