the last 24 hours, 
otherwise 
manual. 
Circuit B Low Suction 
Temperature 
Circuit THR Low Suction 
Temperature 
Compressor A1 Not Started or 
Pressure Increase not 
established 
Compressor A2 Not Started or 
Pressure Increase not 
established 
Compressor B1 Not Started or 
Pressure Increase not 
established 
Compressor B2 Not Started or 
Pressure Increase not 
established 
Compressor THR1 Not Started or 
Pressure Increase not 
established 
Compressor THR2 Not Started or 
Pressure Increase not 
established (RESERVED) 
Unit is in CCN emergency stop 
Circuit A - Repeated high 
discharge gas overrides 
Transducer defective 
or fan circuit 
fault 
Circuit B – Repeated high 
discharge gas overrides 
Circuit THR – Repeated high 
discharge gas overrides 
Circuit A – Repeated low suction 
temp overrides 
Pressure sensor 
defective or 
refrigerant charge too 
low 
Circuit B – Repeated low suction 
temp overrides 
Circuit THR – Repeated low suction 
temp overrides 
Refrigerant Leakage Detection 
The refrigerant leak 
sensor contact is 
open 
Return Fan Status Failure 
Supply Fan Status Failure 
The pre-heater 
overheat feedback is 
open 
Turn off the pre-heaters 
immediately, disable 
pre-heater function. 
Other parts of machine 
like compressor and fan 
remain running 
 
The anti-fire contact 
is open 
the heating stage 
fault contact 
is open 
Turn off the pre-heaters 
immediately, disable 
pre-heater function. 
Other parts of machine 
like compressor and fan 
remain running 
 
The unit is controlled 
by an external 
thermostat and this 
simultaneously sends 
a heating or cooling 
command 
The indoor fan shuts 
down. 
All functions are 
deactivated. 
Service maintenance alert, call 
your maintenance company 
The preventive 
maintenance