Automatic when the 
configuration is 
entered 
The unit size has not 
been configured 
Illegal factory configuration 
Number #1 to nn 
The unit size has 
been configured with 
the wrong value 
Master/Slave communication 
Automatic when 
communication 
is re-established 
CCN installation bus 
defective 
Unit goes into 
autonomous mode 
The airflow filter 
contact is open 
Compressor A High Pressure 
Switch protection 
Compressor B High Pressure 
Switch protection 
Compressor C High Pressure 
Switch protection 
Software problem. 
Unit shuts down 
Software problem. Unit 
shuts down 
EXV stepper motor failure A 
EXV stepper motor failure B 
EXV stepper motor failure THR 
High Suction Superheat THR 
Low Suction Superheat THR 
Fgas check needed, call your 
maintenance company 
Regular FGAS check 
needed 
Possible Excess Building Air 
Leakage, 
Check Doors and Windows 
In some situations or 
occasions 
many doors and 
windows (or Tent 
like structure ) may 
be open so that 
no matter what the 
control does 
the building pressure 
will be close 
to zero. 
Circuit A SIOB Low Voltage Failure 
SIOB board has a 
micro power cut 
All outputs in SIOB 
board are cut off, 
managed by SIOB board 
itself. 
SmartVu will take control 
of SIOB board once the 
board is successfully 
reset. 
Circuit B SIOB Low Voltage Failure 
Circuit C SIOB Low Voltage Failure 
Circuit A Compressor VFD Failure 
Compressor driver 
has detected 
abnormal running 
status of VSPD 
compressor. The 
error relay on the 
driver is opened 
VSPD compressor shuts 
down. 
Once driver error relay 
return back to closed 
state, then compressor 
is allowed to start. 
Return Fan Calibration Not Set 
Return Fan not 
calibrated