VVT Zone Controller 59
– The value that the relative humidity sensor must exceed to
generate a
in the occupied mode if
is set to
D:
.
There is a fixed hysteresis of 5%rh for return to normal.
R:
100%rh
45 to 100%rh
D: – Determines the amount of delay before an occupied RH
alarm is generated when the controller transitions to the occupied mode. The delay
time equals this value multiplied by the difference between the sensor RH value and
the occupied RH setpoint plus 15 minutes.
R:
5 minutes
0 to 30 minutes
Unocc High RH Alarm Limit
– The value that the relative humidity sensor must exceed
to generate a
in the unoccupied mode if
is set to
D:
. There is a fixed hysteresis of 5%rh for return to normal.
R:
100%rh
45 to 100%rh
Occupied High CO2 Alarm Limit
– The value that the CO
2
D:
sensor must exceed to
generate an
in the occupied mode if
is set to
. There is a fixed hysteresis of 100ppm for return to normal.
R:
1100ppm
0 to 9999 ppm
– The fractional portion of an hour determining the amount of
delay before an indoor air quality alarm is generated when the controller transitions to
the occupied mode. The delay time equals this value multiplied by the difference
between the sensor CO
2
D:
value and the setpoint plus 15 minutes.
R:
.25 hr (15 minutes)
0 to 1.0 hr (60 minutes)
Alarms Displayed on SPT Sensor
– If set to display, shows the alarm indicator on the SPT Pro
sensor if the space temperature alarm is active.
D:
R:
Ignore
Ignore/Display
– Shows the alarm indicator on the SPT Pro sensor if the
is active.
D:
R:
Ignore
Ignore/Display
– If set to display, shows the alarm indicator on the SPT Pro and SPT
Pro Plus' sensor if a dirty filter alarm is active.
D:
R:
Display
Ignore/Display
Space High Humidity Alarm
– If set to display, shows the alarm indicator on the SPT
Pro and SPT Pro Plus' sensor if the
is active.
D:
R:
Ignore
Ignore/Display
– Shows the alarm indicator on the SPT Pro sensor if the
is in alarm.
D:
R:
Ignore
Ignore/Display