EasyManua.ls Logo

Carrier VVT Zone - I;O Points

Carrier VVT Zone
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VVT Zone Controller 67
Point Name/Description
Default/Range
Air Source Outdoor Air Temp
Shows the air source’s OAT when
Airside Linkage
Status
is
Active
. If
Airside Linkage Status
is
Not Active
, a “?” is displayed.
R: ? or -56 to 245°F
I/O Points
Navigation:
i-Vu / Field Assistant:
BACview:
Properties
>
I/O Points
N/A
WARNING! Do not change the Value, Offset/Polarity, Exp:Num, I/O Type, Sensor/Actuator
Type, Min/Max, or Resolution I/O configuration parameter for the points listed below. Changing these
parameters could cause improper control and/or equipment damage. Use extreme caution if locking a
point as this may also cause improper control and/or equipment damage.
Point Name/Description
Default/Range
SPT Temp Sensor/Zone Temp
SPT Temp Sensor
- (For the SPT Standard, SPT Plus, and SPT Pro sensors only).
Sensor configurations on the microblock's
Properties
>
Details
tab are listed below.
For more information, consult the Carrier Sensors Installation Guide.
Zone Temp
- do not adjust these settings.
R: -56 to 245°F
Sensor Type:
Min Present Value
- Minimum present value the sensor transmits before indicating
an alarm.
D:
45
Max Present Value
- Maximum present value the sensor transmits before indicating
an alarm.
D: 96
Setpoint Adjustment:
Max Adjust
The amount that a user may adjust the setpoint at the sensors.
D:
R:
5°F
0 to 15°F
Reset setpoint adjust to zero when unoccupied -
Resets the setpoint bias to zero
when the controller transitions to unoccupied.
D: Off
Each Pulse
The amount of time that is added to the total override time each time
a user pushes the sensor's override button.
D:
R:
30:00 mm:ss
0:00 to 1440:00 mm:ss
Max Accum
The maximum amount of override time that can be accumulated
when a user pushes the sensor's override button.
D:
R:
240:00 mm:ss
0:00 to 2000:00 mm:ss
Cancel override
How long a user must push the sensor's override button to cancel
an override.
D:
R:
3 seconds
0 to 60 seconds

Table of Contents

Related product manuals