Appendix A: VVT Zone Controller Points/Properties
68 VVT Zone Controller
Sensor calculation method -
When using multiple SPT sensors, select the process
variable to be passed to the controller.
D:
R:
Avg
Avg, Min, Max
Must be enabled for other BACnet objects to read or write to this
point, and for this point to generate alarms.
D:
Enabled
Do not D: change. zone_temp
– The current voltage of the controller's
input. R: 0 to 5 Vdc
R: – The current voltage of the controller's
input. 0 to 5 Vdc
– The value of the controller's
space temperature sensor input. R: -56 to 245°F
– The current value of the controller's SAT input. R: -56 to 140°F
- The hardware state of the contact used for
Remote Occupancy
Override
.
R: Open/Closed
– This internal input monitors the communication between the controller
and the SPT sensor.
indicates communication is normal.
R: Off/On
- The current value of the controller's
output. R: 0 to 100%
- The current hardware state of the controller's
output. R: Off/On
- The current hardware state of the controller's
output. R: Off/On
- The current hardware state of the controller’s
output. The
function of this output depends on the terminal type.
R: Off/On