VVT Zone Controller 65
Alarms
i-Vu / Field Assistant:
BACview:
>
>
>
– Indicates if the space temperature exceeds the high or low alarm limit. R: Normal/Alarm
– Indicates the space temperature value that caused the space
temperature alarm. This value is only displayed when the
alarm (above)
is in
.
R: -56 to 245°F
– Indicates the value of the space temperature alarm limit that
caused the space temperature alarm condition. Value is only displayed when the
alarm (above) is in
.
R: -56 to 245°F
Indicates if the space temperature sensor fails. R: Normal/Alarm
– Indicates if the occupied CO
2
R:
level exceeds the
Occupied High CO2
Alarm Limit
.
Normal/Alarm
– Indicates if the supply air temperature exceeds the high
temperature alarm limit or drops below the low temperature alarm limit.
R: Normal/Alarm
– Indicates if the filter's runtime hours exceeds the runtime alarm limit. R: Clean/Dirty
– Indicates if the relative humidity exceeds the high RH alarm limit. R: Normal/Alarm
Indicates if the controller is not receiving a valid OAT value over the network. R: Normal/Alarm
– If the controller is the VVT Master,
indicates that it lost
Linkage communications with the air source. If the controller is a slave,
indicates that
it lost Linkage communications with the VVT master.
R: Normal/Alarm
Linkage
i-Vu / Field Assistant:
BACview:
>
>
>
>
Click
Linkage Collector/Linkage Provider
to access the microblock popup's
and
tabs. See the microblock popup's Help files for more detailed
explanations.
– Set the
to the total number of controllers in
the linked system, including the bypass and VVT Master.
D:
R:
1
1 to 32