VVT Zone Controller 65
Alarms
Navigation:
i-Vu / Field Assistant:
BACview:
Properties
>
Equipment
>
Alarms
HOME
>
ALARM
Point Name/Description
Range
Space Temperature
Indicates if the space temperature exceeds the high or low alarm limit. R: Normal/Alarm
Alarming Temperature
Indicates the space temperature value that caused the space
temperature alarm. This value is only displayed when the
Space Temperature
alarm (above)
is in
Alarm
.
R: -56 to 245°F
Alarm Limit Exceeded
Indicates the value of the space temperature alarm limit that
caused the space temperature alarm condition. Value is only displayed when the
Space
Temperature
alarm (above) is in
Alarm
.
R: -56 to 245°F
Space Temp Sensor
Indicates if the space temperature sensor fails. R: Normal/Alarm
Indoor Air Quality
Indicates if the occupied CO
2
R:
level exceeds the
Occupied High CO2
Alarm Limit
.
Normal/Alarm
Supply Air Temperature
Indicates if the supply air temperature exceeds the high
temperature alarm limit or drops below the low temperature alarm limit.
R: Normal/Alarm
Filter
Indicates if the filter's runtime hours exceeds the runtime alarm limit. R: Clean/Dirty
Space Relative Humidity
Indicates if the relative humidity exceeds the high RH alarm limit. R: Normal/Alarm
Network OAT -
Indicates if the controller is not receiving a valid OAT value over the network. R: Normal/Alarm
Airside Linkage Status
If the controller is the VVT Master,
Alarm
indicates that it lost
Linkage communications with the air source. If the controller is a slave,
Alarm
indicates that
it lost Linkage communications with the VVT master.
R: Normal/Alarm
Linkage
Navigation:
i-Vu / Field Assistant:
BACview:
Properties
>
Equipment
>
Linkage
HOME
>
CONFIG
>
LINKAGE
Point Name/Description
Default/Range
Airside Linkage
Click
Linkage Collector/Linkage Provider
to access the microblock popup's
Summary
and
Details
tabs. See the microblock popup's Help files for more detailed
explanations.
Linkage
Collector
Set the
Number of Providers
to the total number of controllers in
the linked system, including the bypass and VVT Master.
D:
R:
1
1 to 32