EasyManua.ls Logo

Carrier VVT Zone - Specifications

Carrier VVT Zone
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VVT Zone Controller 3
Specifications
Driver drv_vvtopen
Maximum number of control
programs
1
Power 24 Vac ±10%, 5060 Hz
14 VA power consumption (20 VA with BACview
BACnet port
attached)
26 Vdc (25 V min, 30 V max)
Single Class 2 source only, 100 VA or less
For communication with the controller network using MS/TP (9600 bps, 19.2
kbps, 38.4 kbps, or 76.8 kbps)
Rnet port
For SPT sensors and a BACview
6
1 SPT Plus or SPT Pro
in any of the following combinations, wired in
a daisy-chain configuration:
1–4 SPT Standards
1–4 SPT Standards, and 1 SPT Plus or SPT Pro
Any of the above combinations, plus a BACview
6,
Local Access port
but no more than 6
devices total
For system start-up and troubleshooting using Field Assistant or BACview
6
Inputs
(115.2 kbps)
4 inputs for connecting the following types of sensors:
An alternate space temperature sensor (#33ZCT55SPT)
Supply air temperature sensor (#33ZCSENSAT)
Duct air temperature sensor (#33ZCSENDAT)
CO2 sensor (#33ZCSENCO2)
Relative humidity sensor (#33ZCSENSRH-01 [indoor space] or
33ZCSENDRH-01 [duct])
Remote occupancy sensor
Input resolution 10 bit A/D
Digital outputs 3 digital outputs, relay contact rated at 1 A max. @ 24 Vac/Vdc. Configured
normally open.
Analog output 1 analog output, 010 Vdc (5 mA max). The controlled device must have a
minimum of 2000 Ohms resistance measured from its input to ground and
must share the same ground as the controller.
Output resolution 8 bit D/A
Integral actuator Brushless DC motor, torque 35 inch-pounds (4 Nm), runtime 205 seconds for
90 degree travel during control, or 25 seconds in high-speed test and balance
mode
Battery 10-year Lithium CR2032 battery provides a minimum of 10,000 hours of data
retention during power outages
Protection Incoming power and network connections are protected by non-replaceable
internal solid-state polyswitches that reset themselves when the condition that
causes a fault returns to normal. The power, network, input, and output
connections are also protected against voltage transient and surge events.
BT485 connector You attach a BT485 (not included) to a controller at the beginning and end of
a network segment to add bias and to terminate a network segment.

Table of Contents

Related product manuals