APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.
IAQ INDOOR AIR QUALITY CFG.
DCV.C DCV ECONOMIZER SETPOINTS
EC.MN
Economizer Min.Position 0 to 100 % ECONOMIN 5 22,26,27,67,
72
IAQ.M IAQ Demand Vent Min.Pos. 0 to 100 % IAQMINP 0 26,67,72
AQ.CF AIR QUALITY CONFIGS
IQ.A.C
IAQ Analog Sensor Config 0 to 4 (multi-text strings) IAQANCFG 0 26,27,30,67,
72
IQ.A.F IAQ 4-20 ma Fan Config 0 to 2 (multi-text strings) IAQANFAN 0 26,67,72
IQ.I.C IAQ Discrete Input Config 0 to 2 (multi-text strings) IAQINCFG 0 26,72
IQ.I.F IAQ Disc.In. Fan Config 0 to 2 (multi-text strings) IAQINFAN 0 26,72
OQ.A.C OAQ 4-20ma Sensor Config 0 to 2 (multi-text strings) OAQANCFG 0 26,72
AQ.SP AIR QUALITY SETPOINTS
IQ.O.P IAQ Econ Override Pos. 0 to 100 % IAQOVPOS 100 26,72,108
DAQ.L Diff.Air Quality LoLimit 0 to 1000 DAQ_LOW 100 72
DAQ.H Diff.Air Quality HiLimit 100 to 2000 DAQ_HIGH 700 72
D.F.OF DAQ PPM Fan Off Setpoint 0 to 2000 DAQFNOFF 200 27,27,72
D.F.ON DAQ PPM Fan On Setpoint 0 to 2000 DAQFNON 400 27,27,72
IAQ.R Diff. AQ Responsiveness 5 to 5 IAQREACT 0 72
OAQ.L OAQ Lockout Value 0 to 2000 OAQLOCK 0 72
OAQ.U User Determined OAQ 0 to 5000 OAQ_USER 400 27,72
AQ.S.R AIR QUALITY SENSOR RANGE
IQ.R.L IAQ Low Reference 0 to 5000 IAQREFL 0 27,72,73
IQ.R.H IAQ High Reference 0 to 5000 IAQREFH 2000 27,72,73
OQ.R.L OAQ Low Reference 0 to 5000 OAQREFL 0 72,73
OQ.R.H OAQ High Reference 0 to 5000 OAQREFH 2000 72,73
IAQ.P IAQ PRE-OCCUPIED PURGE
IQ.PG IAQ Purge Yes/No IAQPURGE No 72,73
IQ.P.T IAQ Purge Duration 5 to 60 min IAQPTIME 15 72,73
IQ.P.L IAQ Purge LoTemp Min Pos 0 to 100 % IAQPLTMP 10 72,73
IQ.P.H IAQ Purge HiTemp Min Pos 0 to 100 % IAQPHTMP 35 72,73
IQ.L.O IAQ Purge OAT Lockout 35 to 70 dF IAQPNTLO 50 72,73
DEHU DEHUMIDIFICATION CONFIG.
D.SEL Dehumidification Config 0 to 3 (multi-text strings) DHSELECT 0 74
D.SEN Dehumidification Sensor 1 to 2 (multi-text strings) DHSENSOR 1 74
D.EC.D Econ disable in DH mode? Yes/No DHECDISA Yes 74
D.V.CF Vent Reheat Setpt Select 0 to 1 (multi-text strings) DHVHTCFG 0 74
D.V.RA Vent Reheat RAT offset 0 to 8 ^F DHVRAOFF 0 74
D.V.HT Vent Reheat Setpoint 55 to 95 dF DHVHT_SP 70 74
D.C.SP Dehumidify Cool Setpoint 40 to 55 dF DHCOOLSP 45 74
D.RH.S Dehumidify RH Setpoint 10 to 90 % DHRELHSP 55 74
HZ.RT Humidimizer Adjust Rate 5 to 120 HMZRRATE 30 74
DH.DB Dehumidify RH Deadband 1 to 30 % DHSENSDB
DH.TG Dehum Discrete Timeguard 10 to 90 s DHDISCTG
HZ.PG Humidimizer Prop. Gain 0 to 10 HMZR_PG 0.8 74
HZ.OR Enable HMZR ST Oil Ret Disable/Enable ENHORTST Enable 74
CCN CCN CONFIGURATION
CCNA CCN Address 1 to 239 CCNADD 1 77
CCNB CCN Bus Number 0 to 239 CCNBUS 0 77
BAUD CCN Baud Rate 1 to 5 (multi-text strings) CCNBAUDD 3 77
BROD CCN BROADCST DEFINITIONS
TM.DT CCN Time/Date Broadcast ON/OFF CCNBC On 77
OAT.B CCN OAT Broadcast ON/OFF OATBC Off 77
ORH.B CCN OARH Broadcast ON/OFF OARHBC Off 77
OAQ.B CCN OAQ Broadcast ON/OFF OAQBC Off 77
G.S.B Global Schedule Broadcst ON/OFF GSBC Off 77
B.ACK CCN Broadcast Ack'er ON/OFF CCNBCACK Off 77
SC.OV CCN SCHEDULES-OVERRIDES
SCH.N Schedule Number 0 to 99 SCHEDNUM 1 21,77
HOL.T Accept Global Holidays? YES/NO HOLIDAYT No 77
O.T.L Override Time Limit 0 to 4 HRS OTL 1 77
OV.EX Timed Override Hours 0 to 4 HRS OVR_EXT 0 77
SPT.O SPT Override Enabled ? YES/NO SPT_OVER Yes 77,78
T58.O T58 Override Enabled ? YES/NO T58_OVER Yes 77,78
GL.OV Global Sched. Override ? YES/NO GLBLOVER No 77,78