APPENDIX B — CCN TABLES (cont)
SERVICE-CONFIG TABLES
TABLE NAME RANGE UNITS POINT NAME DEFAULT
ALLM
SPT lo alert limit/occ –10 to 245 dF SPLO 60
SPT hi alert limit/occ –10 to 245 dF SPHO 85
SPT lo alert limit/unocc –10 to 245 dF SPLU 45
SPT hi alert limit/unocc –10 to 245 dF SPHU 100
EDT lo alert limit/occ –40 to 245 dF SALO 40
EDT hi alert limit/occ –40 to 245 dF SAHO 100
EDT lo alert limit/unocc –40 to 245 dF SALU 40
EDT hi alert limit/unocc –40 to 245 dF SAHU 100
RAT lo alert limit/occ –40 to 245 dF RALO 60
RAT hi alert limit/occ –40 to 245 dF RAHO 90
RAT lo alert limit/unocc –40 to 245 dF RALU 40
RAT hi alert limit/unocc –40 to 245 dF RAHU 100
RARH low alert limit 0 to 100 % RRHL 0
RARH high alert limit 0 to 100 % RRHH 100
SP low alert limit 0 to 5 " H2O SPL 0
SP high alert limit 0 to 5 " H2O SPH 2
BP lo alert limit –0.25 to 0.25 " H2O BPL -0.25
BP high alert limit –0.25 to 0.25 " H2O BPH 0.25
IAQ high alert limit 0 to 5000 IAQH 1200
BP__
Building Press. Config 0 to 3 BLDG_CFG 0
Bldg.Pres.PID Run Rate 5 to 120 BPIDRATE 10
Bldg. Press. Prop. Gain 0 to 5 BLDGP_PG 0.5
Bldg.Press.Integ.Gain 0 to 2 BLDGP_IG 0.5
Bldg.Press.Deriv.Gain 0 to 5 BLDGP_DG 0.3
BP Setpoint Offset 0.0 to 0.5 BPSO 0.05
BP VFD Minimum Speed 0 to 100 BLDGPMIN 10
BP VFD Maximum Speed 0 to 100 BLDGPMAX 100
VFD/Act. Fire Speed/Pos. 0 to 100 BLDGPFSO 100
Power Exhaust Motors 0 to 2 PWRM 1
0=None,1=4 Mtr, 2=6 Mtr
Building Pressure Sensor Enable/Disable BPSENS Dsable
Bldg Press (+/-) Range 0 to 1 BP_RANGE 0.25
Building Pressure Setp. –0.25 -> 0.25 " H2O BPSP 0.05
Power Exhaust On Setp.1 0 to 100 % PES1 35
Power Exhaust On Setp.2 0 to 100 % PES2 75
Modulating PE Alg. Slct. 1 to 3 BPSELECT 1
BP PID Evaluation Time 0 to 10 min BPPERIOD 1
BP Threshold Adjustment 0.1 to 10 BPZ_GAIN 1
High BP Level 0 to 1 BPHPLVL 0.05
Low BP Level 0 to 1 BPLPLVL 0.04
COOL
Capacity Threshold Adjust –10 to 10 Z_GAIN 1
Compressor Lockout Temp –20 to 55 dF OATLCOMP 40
Fan-off Delay, Mech Cool 0 to 600 sec COOL_FOD 60
Minimum Load Valve? (HGBP) Yes/No MLV_SEL No
Motor Master Control ? Yes/No MOTRMAST No
Head Pressure Setpoint 80 to 150 dF HPSP 100
Enable Compressor A1 Enable/Disable CMPA1ENA Enable
Enable Compressor A2 Enable/Disable CMPA2ENA Enable
Enable Compressor B1 Enable/Disable CMPB1ENA Enable
Enable Compressor B2 Enable/Disable CMPB2ENA Enable
CSB A1 Feedback Alarm Enable/Disable CSB_A1EN Enable
CSB A2 Feedback Alarm Enable/Disable CSB_A2EN Enable
CSB B1 Feedback Alarm Enable/Disable CSB_B1EN Enable
CSB B2 Feedback Alarm Enable/Disable CSB_B2EN Enable
Rev. Rotation Verified ? Yes/No REVR_VER No
Hi SST Alert Delay Time 5 to 30 min HSSTTIME 10
Enable Digital Scroll Yes/No DIGCMPEN No
DS Min Digital Capacity 25 to 100 % MINCAPDS 50
Dig Scroll Adjust Delta 0 to 100 % DSADJPCT 100
Dig Scroll Adjust Delay 15 to 60 sec DSADJDLY 20
Dig Scroll Reduce Delta 0 to 100 % DSREDPCT 6
Dig Scroll Reduce Delay 15 to 60 sec DSREDDLY 30
Dig Scroll Reduction OAT 70 to 120 dF DSREDOAT 95
Dig Scroll Max Only OAT 70 to 120 dF DSMAXOAT 105
MM Setpoint Offset –20 to 20 dF MMSPOFST –10
MotorMaster Prop Gain 0 to 5 MM_PG 1
MotorMaster Integ. Time 0.5 to 50 MM_TI 30
Motor Master PI Run Rate 5 to 120 secs MM_RATE 5
Outdoor VFD PI Run Rate 5-120 secs OV_RATE
Outdoor VFD Prop. Gain 0-5 OV_PG
Outdoor VFD Integ. Time 0.5 - 200 secs OV_TI
Outdoor VFD Anti-Windup 0.1 - 1 OV_AU
Outdoor VFD SCT DeadBand 0 - 20 degF OV_SCTDB
Outdoor VFD Dehum-RH SPD 0 - 100 % OV_RH
Outdoor VFD MvgAvgFltrPt OV_MAFP