166
 APPENDIX B ā CCN TABLES (cont)
CONFIG TABLES (cont)
TABLE NAME RANGE UNITS POINT NAME DEFAULT
SCHEDOVR
Schedule Number 0 to 99 SCHEDNUM 0
Accept Global Holidays? Yes/No HOLIDAYT No
Override Time Limit 0 to 4 hours OTL 1
Timed Override Hours 0 to 4 hours OVR_EXT 0
Accepting an Override:
  SPT Override Enabled ? Yes/No SPT_OVER Yes
  T58 Override Enabled ? Yes/No T58_OVER Yes
Allowed to Broadcast a
Global Sched. Override ? Yes/No GLBLOVER No
SET_PNT
Occupied Heat Setpoint 55 to 80 dF OHSP 68
Occupied Cool Setpoint 55 to 80 dF OCSP 75
Unoccupied Heat Setpoint 40 to 80 dF UHSP 55
Unoccupied Cool Setpoint 75 to 95 dF UCSP 90
Heat-Cool Setpoint Gap 2 to 10 ^F HCSP_GAP 5
VAV Occ. Cool On Delta 0 to 25 ^F VAVOCON 3.5
VAV Occ. Cool Off Delta 1 to 25 ^F VAVOCOFF 2
Supply Air Setpoint 45 to 75 dF SASP 55
Supply Air Setpoint Hi 45 to 75 dF SASP_HI 55
Supply Air Setpoint Lo 45 to 75 dF SASP_LO 60
Heating Supply Air Setpt 90 to 145 dF SASPHEAT 85
Tempering Purge SASP ā20 to 80 dF TEMPPURG 50