165
APPENDIX B — CCN TABLES (cont)
CONFIG TABLES
TABLE NAME RANGE UNITS POINT NAME DEFAULT
ALARMDEF
Alarm Routing Control 00000000 to 11111111 ALRM_CNT 11000000
Equipment Priority 0 to 7 EQP_TYPE 5
Comm Failure Retry Time 1 to 240 min RETRY_TM 10
Re-Alarm Time 1 to 255 min RE-ALARM 30
Alarm System Name up to 8 alphanum ALRM_NAM A-SERIES
BRODEFS
CCN Time/Date Broadcast Off/On CCNBC Off
CCN OAT Broadcast Off/On OATBC Off
CCN OARH Broadcast Off/On OARHBC Off
CCN OAQ Broadcast Off/On OAQBC Off
Global Schedule Broadcst Off/On GSBC Off
Daylight Savings Start:
Month 1 to 12 STARTM 4
Week 1 to 5 STARTW 1
Day 1 to 7 STARTD 7
Minutes to Add 0 to 90 MINADD 60
Daylight Savings Stop:
Month 1 to 12 STOPM 10
Week 1 to 5 STOPW 5
Day 1 to 7 STOPD 7
Minutes to Subtract 0 to 90 MINSUB 60
Ctlr-ID
Device Name: A-Series
Description: A Series Rooftop
Location:
Software Part Number: CESR131343-XX-XX
Model Number:
Serial Number:
Reference Number:
HOLIDAY Broadcast Supervisory
HOLDY01S Holiday Start Month 1 to 12 HOL-MON 0
to Start Day 1 to 31 HOL-DAY 0
HOLDY30S Duration (days) 1 to 99 HOL-LEN 0
OCCDEFCS Occupancy Supervisory
Timed Override Hours 0 OVR-EXT
Period 1 DOW (MTWTFSSH) 00000000 DOW1
Occupied From 0:00 OCCTOD1
Occupied To 0:00 UNOCTOD1
Period 2 DOW (MTWTFSSH) 00000000 DOW2
Occupied From 0:00 OCCTOD2
Occupied To 0:00 UNOCTOD2
Period 3 DOW (MTWTFSSH) 00000000 DOW3
Occupied From 0:00 OCCTOD3
Occupied To 0:00 UNOCTOD3
Period 4 DOW (MTWTFSSH) 00000000 DOW4
Occupied From 0:00 OCCTOD4
Occupied To 0:00 UNOCTOD4
Period 5 DOW (MTWTFSSH) 00000000 DOW5
Occupied From 0:00 OCCTOD5
Occupied To 0:00 UNOCTOD5
Period 6 DOW (MTWTFSSH) 00000000 DOW6
Occupied From 0:00 OCCTOD6
Occupied To 0:00 UNOCTOD6
Period 7 DOW (MTWTFSSH) 00000000 DOW7
Occupied From 0:00 OCCTOD7
Occupied To 0:00 UNOCTOD7
Period 8 DOW (MTWTFSSH) 00000000 DOW8
Occupied From 0:00 OCCTOD8
Occupied To 0:00 UNOCTOD8