APPENDIX B — CCN TABLES (cont)
STATUS DISPLAY TABLES (cont)
SETPOINT TABLE
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
UOUTPUTS
FANS
Supply Fan Relay On/Off SFAN_RLY
Supply Fan VFD Speed 0 to 100 % SFAN_VFD
Supply Fan Request Yes/No SFANFORC forcible
Exhaust Fan VFD Speed 0 to 100 % EFAV_VFD
Power Exhaust Relay A On/Off PE_A
Power Exhaust Relay B On/Off PE_B
Power Exhaust Relay C On/Off PE_C
Condenser Fan A On/Off CONDFANA
Condenser Fan B On/Off CONDFANB
ODF_VFD-A Actual Speed % 0 to 100 % OVA_SPD
ODF_VFD-B Actual Speed % 0 to 100 % OVB_SPD
MtrMaster A Commanded % 0 to 100 MM_A_VFD
MtrMaster B Commanded % 0 to 100 MM_B_VFD
MotorMaster Fan Circuit A On/Off MM_A_RUN
MotorMaster Fan Circuit B On/Off MM_B_RUN
COOLING
Compressor A1 Relay On/Off CMPA1
Compressor A2 Relay On/Off CMPA2
Minimum Load Valve On/Off MLV
Digital Scroll Capacity 20 to 100 % CMPDSCAP
Compressor B1 Relay On/Off CMPB1
Compressor B2 Relay On/Off CMPB2
Humidimizer 3-Way Valve 0 to 100 HUM3WVAL
Condenser EXV Position 0 to 100 COND_EXV
Bypass EXV Position BYP_EXV
HEATING
Heat Relay 1 On/Off HS1
Heat Relay 2 On/Off HS2
Relay 3 W1 Gas Valve 2 On/Off HS3
Relay 4 W2 Gas Valve 2 On/Off HS4
Relay 5 W1 Gas Valve 3 On/Off HS5
Relay 6 W2 Gas Valve 3 On/Off HS6
Heat Interlock Relay On/Off HIR forcible
ECONOMIZER
Economizer Act.Curr.Pos. 0 to 100 % ECONOPOS
Economizer Act.Cmd.Pos. 0 to 100 % ECONOCMD forcible
Economizer Power Relay On/Off ECON_PWR forcible
GENERAL OUTPUTS
Remote Alarm/Aux Relay On/Off ALRM forcible
TABLE NAME RANGE UNITS POINT NAME DEFAULT
SET_PNT
Occupied Heat Setpoint 40 to 99 dF OHSP 68
Occupied Cool Setpoint 40 to 99 dF OCSP 75
Unoccupied Heat Setpoint 40 to 99 dF UHSP 55
Unoccupied Cool Setpoint 40 to 99 dF UCSP 90
Heat-Cool Setpoint Gap 2 to 10 ^F HCSP_GAP 5
VAV Occ. Cool On Delta 0 to 25 ^F VAVOCON 3.5
VAV Occ. Cool Off Delta 1 to 25 ^F VAVOCOFF 2
Supply Air Setpoint 45 to 75 dF SASP 55
Supply Air Setpoint Hi 45 to 75 dF SASP_HI 55
Supply Air Setpoint Lo 45 to 75 dF SASP_LO 60
Heating Supply Air Setpt 80 to 100 dF SASPHEAT 85
Tempering Purge SASP –20 to 80 dF TEMPPURG 50
Tempering in Cool SASP 5 to 75 dF TEMPCOOL 5
Tempering in Vent Occ SASP –20 to 80 dF TEMPVOCC 65
Tempering Vent Unocc. SASP –20 to 80 dF TEMPVUNC 50