APPENDIX B — CCN TABLES (cont)
STATUS DISPLAY TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
TEMPCTRL
Evaporator Discharge Tmp dF EDT
Leaving Air Temperature dF LAT
Mixed Air Temperature dF MAT
Controlling Return Temp dF RETURN_T forcible
Controlling Space Temp dF SPACE_T forcible
TEMPS
Air Temp Lvg Supply Fan dF SAT
Return Air Temperature dF RAT forcible
Outside Air Temperature dF OAT forcible
Space Temperature dF SPT forcible
Space Temperature Offset ^F SPTO forcible
Staged Gas LAT Sum dF LAT_SGAS
Staged Gas LAT 1 dF LAT1SGAS
Staged Gas LAT 2 dF LAT2SGAS
Staged Gas LAT 3 dF LAT23SGAS
Staged Gas Limit Sw.Temp dF LIMSWTMP
Cir A Sat.Condensing Tmp dF SCTA
Cir B Sat.Condensing Tmp dF SCTB
Cir A Sat.Suction Temp. dF SSTA
Cir B Sat.Suction Temp. dF SSTB
DS Discharge Temperature dF DTDS
TSTAT
Control Mode………..: ascii text strings
Thermostat Y1 Input On/Off Y1 forcible
Thermostat Y2 Input On/Off Y2 forcible
Thermostat W1 Input On/Off W1 forcible
Thermostat W2 Input On/Off W2 forcible
Thermostat G Input On/Off G forcible
UINPUTS
Filter Status Input Dirty/Clean FLTS forcible
Fan request from IGC On/Off IGCFAN
Fire Shutdown Switch Alarm/Normal FSD forcible
Thermostat G Input On/Off G forcible
Thermostat W2 Input On/Off W2 forcible
Thermostat W1 Input On/Off W1 forcible
Thermostat Y2 Input On/Off Y2 forcible
Thermostat Y1 Input On/Off Y1 forcible
Economizer Control Input On/Off ECOSW forcible
Remote Economizer Enable Yes/No ECONENBL forcible
Econo Position Override Yes/No ECOORIDE forcible
Remote Input State On/Off RMTIN forcible
Supply Fan Status Switch On/Off SFS forcible
Demand Limit Switch 1 On/Off DMD_SW1 forcible
Demand Limit Switch 2 On/Off DMD_SW2 forcible
Pressurization Input Alarm/Normal PRES forcible
Evacuation Input Alarm/Normal EVAC forcible
Smoke Purge Input Alarm/Normal PURG forcible
IAQ - Discrete Input High/Low IAQIN forcible
Dehumidify Switch Input On/Off DHDISCIN forcible