EasyManua.ls Logo

Carrier WEATHERMAKER 48A2020 - Page 162

Carrier WEATHERMAKER 48A2020
230 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
162
APPENDIX B — CCN TABLES (cont)
STATUS DISPLAY TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
GENERAL
Occupied ? Yes/No OCCUPIED forcible
Static Pressure " H2O SP
Building Pressure " H2O BP
Outside Air Rel.Humidity % OARH forcible
Return Air Rel.Humidity % RARH forcible
Space Temperature Offset ^F SPTO forcible
Supply Air Setpnt. Reset ^F SASPRSET forcible
Static Pressure Reset SPRESET forcible
IAQ - PPM Return CO2 IAQ forcible
OAQ - PPM Return CO2 OAQ forcible
IAQ Min.Pos.Override % IAQMINOV forcible
GENERIC
20 points dependent upon the configura-
tion of the “generics” table in the Service-
Config section starting on page 167.
HEATING
HVAC Mode…………..: ascii text strings
Control Mode………..: ascii text strings
Heat Control Type……: ascii text strings
Re-Heat Control Type ascii text strings
Heating Mode………..: ascii text strings
Current Heat Stage HT_STAGE
Heating Control Point dF HEATCPNT
Heat Relay 1 HS1
Heat Relay 2 HS2
Relay 3 W1 Gas Valve 2 HS3
Relay 4 W2 Gas Valve 2 HS4
Relay 5 W1 Gas Valve 3 HS5
Relay 6 W2 Gas Valve 3 HS6
Heat Interlock Relay HIR forcible
Heat Stage 1 Timeguard HS1_TG
Heat Stage 2 Timeguard HS2_TG
Heat Stage 3 Timeguard HS3_TG
Heat Stage 4 Timeguard HS4_TG
Heat Stage 5 Timeguard HS5_TG
Heat Stage 6 Timeguard HS6_TG
HMZR
HVAC Mode……… Ascii text strings
Humidimizer Capacity 0 to 100 % HMZRCAPC
Condenser EXV Position 0 to 100 % COND_EXV
Bypass EXV Position 0 to 100 % BYP_EXV
Humidimizer #-Way Valve On/Off HUM3WVAL
Cooling Control Point –20 to 140 DF COOLCPNT
Evaporator Discharge Tmp –40 to 240 DF EDT
Heating Control Point –20 to 140 DF HEATCPNT
Leaving Air Tmp –40 to 240 DF LAT
MODEDISP
System Mode…………: ascii text strings
HVAC Mode…………..: ascii text strings
Control Mode………..: ascii text strings
Currently Occupied On/Off MODEOCCP
Timed Override in effect On/Off MODETOVR
DCV resetting min pos On/Off MODEADCV
Supply Air Reset On/Off MODESARS
Demand Limit in Effect On/Off MODEDMLT
Temp.Compensated Start On/Off MODETCST
IAQ pre-occ purge active On/Off MODEIQPG
Linkage Active - DAV On/Off MODELINK
Mech.Cooling Locked Out On/Off MODELOCK
HVAC Mode Numerical Form number MODEHVAC
MODETRIP
Unoccup. Cool Mode Start UCCLSTRT
Unoccup. Cool Mode End UCCL_END
Occupied Cool Mode Start OCCLSTRT
Occupied Cool Mode End OCCL_END
Ctl.Temp RAT,SPT or Zone CTRLTEMP
Occupied Heat Mode End OCHT_END
Occupied Heat Mode Start OCHTSTRT
Unoccup. Heat Mode End UCHT_END
Unoccup. Heat Mode Start UCHTSTRT
HVAC Mode…………..: ascii text strings string

Table of Contents

Related product manuals