175
APPENDIX B — CCN TABLES (cont)
MAINTENANCE DISPLAY TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
MODES
System Mode…………: ascii text strings
HVAC Mode…………..: ascii text strings
Control Mode………..: ascii text strings
Currently Occupied On/Off MODEOCCP
Timed Override in effect On/Off MODETOVR
DCV resetting min pos On/Off MODEADCV
Supply Air Reset On/Off MODESARS
Demand Limit in Effect On/Off MODEDMLT
Cir A HighAmb at startup On/Off MODEHS_A
Cir B HighAmb at startup On/Off MODEHS_B
Temp.Compensated Start On/Off MODETCST
IAQ pre-occ purge active On/Off MODEIQPG
Linkage Active - DAV On/Off MODELINK
Mech.Cooling Locked Out On/Off MODELOCK
HVAC Mode Numerical Form 0 to 24 MODEHVAC
OCCDEFME
Current Day, Time & Date: ascii date & time TIMEDATE
Occupancy Controlled By: ascii text OCDFTXT1
ascii text OCDFTXT2
ascii text OCDFTXT3
Currently Occupied Yes/No MODE_OCC
Current Occupied Time STRTTIME
Current Unoccupied Time ENDTIME
Next Occupied Day & Time NXTOC_DT
Next Unocc. Day & Time NXTUN_DT
Last Unocc. Day & Time PRVUN_DT
Current Occup. Period # PER_NO
Timed-Override in Effect Yes/No OVERLAST
Timed-Override Duration hours OVR_HRS
PRESBLDG
Building Pressure " H2O BP
Econo Damper Current Pos % ECONOPOS
Power Exhaust Stage A PE_A
Power Exhaust Stage B PE_B
Power Exhaust Stage C PE_C
BP Load Factor BPSMZ
BP Rise Per Stage BPRISE
BP PID/Integral Term BPINT config
BP PID Threshold BPZ config
BP Deadband BPY config
Building Pressure Error BPERROR config
Rate of Chng of BPERROR BPRATE config
High BP Override BPHPOVRD config
Low BP Override BPLPOVRD config
PRESDUCT
Static Pressure " H2O SP
Supply Fan VFD Speed % SFAN_VFD
Static Pressure Setpoint " H2O SPSP config
Static Pressure Reset SPRESET forcible
STAGEGAS
Heating Mode………..:
Requested Heat Stage HT_STAGE
Heating Control Point HEATCPNT
Staged Gas LAT Sum dF LAT_SGAS
Staged Gas LAT 1 dF LAT1SGAS
Staged Gas LAT 2 dF LAT2SGAS
Staged Gas LAT 3 dF LAT3SGAS
Staged Gas Limit Sw.Temp dF LIMSWTMP
Heat PID Timer sec HTSGTIMR
Staged Gas Capacity Calc % HTSGCALC
Current Running Capacity % HTSG_CAP
Proportional Cap. Change HTSG_P
Derivative Cap. Change HTSG_D
Maximum Heat Stages HTMAXSTG
Hi Limit Switch Tmp Mode LIMTMODE
LAT Cutoff Mode LATCMODE
Capacity Clamp Mode CAPMODE
STRTHOUR
Compressor A1 Run Hours hours HR_A1 config
Compressor A2 Run Hours hours HR_A2 config
Compressor B1 Run Hours hours HR_B1 config
Compressor B2 Run Hours hours HR_B2 config
Compressor A1 Starts CY_A1 config
Compressor A2 Starts CY_A2 config
Compressor B1 Starts CY_B1 config
Compressor B2 Starts CY_B2 config