Table 90 — Auto View of Run Status Display Table
Table 91 — Economizer Run Status Display Table
Table 92 — Cooling Information Display Table
ITEM EXPANSION RANGE UNITS POINT WRITE STATUS
VIEW AUTO VIEW OF RUN STATUS
HVAC ascii string spelling out the hvac modes string
OCC Occupied ? YES/NO OCCUPIED forcible
MAT Mixed Air Temperature dF MAT
EDT Evaporator Discharge Tmp dF EDT
LAT Leaving Air Temperature dF LAT
EC.C.P Economizer Control Point dF ECONCPNT
ECN.P Economizer Act.Curr.Pos. 0 to 100 % ECONOPOS
CL.C.P Cooling Control Point dF COOLCPNT
C.CAP Current Running Capacity CAPTOTAL
HT.C.P Heating Control Point dF HEATCPNT
HT.ST Requested Heat Stage HT_STAGE
H.MAX Maximum Heat Stages HTMAXSTG
ITEM EXPANSION RANGE UNITS POINT WRITE STATUS
ECON ECONOMIZER RUN STATUS
ECN.P Economizer Act.Curr.Pos. 0 to 100 % ECONOPOS
ECN.C Economizer Act.Cmd.Pos. 0 to 100 % ECONOCMD forcible
ACTV Economizer Active ? YES/NO ECACTIVE
DISA ECON DISABLING CONDITIONS
UNAV Econ Act. Unavailable? YES/NO ECONUNAV
R.EC.D Remote Econ. Disabled? YES/NO ECONDISA
DBC DBC - OAT Lockout? YES/NO DBC_STAT
DEW DEW - OA Dewpt.Lockout? YES/NO DEW_STAT
DDBC DDBD- OAT > RAT Lockout? YES/NO DDBCSTAT
OAEC OAEC- OA Enth Lockout? YES/NO OAECSTAT
DEC DEC - Diff.Enth.Lockout? YES/NO DEC_STAT
EDT EDT Sensor Bad? YES/NO EDT_STAT
OAT OAT Sensor Bad ? YES/NO OAT_STAT
FORC Economizer Forced ? YES/NO ECONFORC
SFON Supply Fan Not On 30s ? YES/NO SFONSTAT
CLOF Cool Mode Not In Effect? YES/NO COOL_OFF
OAQL OAQ Lockout in Effect ? YES/NO OAQLOCKD
HELD Econ Recovery Hold Off? YES/NO ECONHELD
DH.DS Dehumid Desabled Econ? YES/NO DHDISABL
O.AIR OUTSIDE AIR INFORMATION
OAT Outside Air Temperature dF OAT forcible
OA.RH Outside Air Rel. Humidity % OARH forcible
OA.E Outside Air Enthalpy OAE
OA.D.T OutsideAir Dewpoint Temp dF OADEWTMP
ITEM EXPANSION RANGE UNITS POINT WRITE STATUS
COOL COOLING INFORMATION
C.CAP Current Running Capacity % CAPTOTAL
CUR.S Current Cool Stage COOL_STG
MAX.S Maximum Cool Stages CLMAXSTG
DEM.L Active Demand Limit % DEM_LIM forcible
SUMZ COOL CAP. STAGE CONTROL
SMZ
Capacity Load Factor –100  
+100
SMZ
ADD.R Next Stage EDT Decrease ^F ADDRISE
SUB.R Next Stage EDT Increase ^F SUBRISE
R.PCT Rise Per Percent Capacity RISE_PCT
Y.MIN Cap Deadband Subtracting Y_MINUS
Y.PLU Cap Deadband Adding Y_PLUS
Z.MIN Cap Threshold Subtracting Z_MINUS
Z.PLU Cap Threshold Adding Z_PLUS
H.TMP High Temp Cap Override HI_TEMP
L.TMP Low Temp Cap Override LOW_TEMP
PULL Pull Down Cap Override PULLDOWN
SLOW Slow Change Cap Override SLO_CHNG
HMZR HUMIDIMIZER
  CAPC Humidimizer Capacity HMZRCAPC
  C.EXV Condenser EXV Position COND_EXV
  B.EXV Bypass EXV Position BYP_EXV
  RHV Humidimizer 3-Way Valve HUM3WVAL
  C.CPT Cooling Control Point COOLCPNT
  EDT Evaporator Discharge Tmp EDT
  H.CPT Heating Control Point HEATCPNT
  LAT Leaving Air Temperature LAT