EasyManua.ls Logo

Cascade TEK TFO-1 - Air Flow Performance

Cascade TEK TFO-1
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
45 | Page
UNIT SPECIFICATIONS
Recovery Time: From a 30-second door opening.
Model Recovery to 80°C Recovery to 150° Recovery to 306°C
TFO-1 1.5 Minutes
4.5 Minutes
14.0 Minutes
TFO-3 1.5 Minutes 2.0 Minutes
18.0 Minutes
TFO-5 2.0 Minutes 4.0 Minutes
45.0 Minutes
Recovery Time: From a 60-second door opening.
Model Recovery to 80°C Recovery to 150° Recovery to 306°C
TFO-1 4.0 Minutes 6.0 Minutes
20.0 Minutes
TFO-3 2.0 Minutes
4.5 Minutes
36.0 Minutes
TFO-5 3.5 Minutes 6.0 Minutes
57.0 Minutes
AIR FLOW PERFORMANCE
Ventilation Rates
Model Cubic Feet per Minute @80°C Liters per Minute @80°C
TFO-1
5.6
158.6
TFO-3
11.3
320.0
TFO-5
15.2
430.4
Air Changes per Hour
Model @80°C
TFO-1
330
TFO-3 225
TFO-5 180
Air Velocity Across Shelf Space
Model Linear Feet per Minute Meters per Minute
TFO-1
125
38.1
TFO-3
140 42.7
TFO-5
145 44.2