22
Effect: Any current chilling cycle is interrupted.
If a storage phase is in progress, the compressor and the fan set to stand-by sta-
tus.
When the appliance is in Stop status, press Start to set the compressor and fan
to stand by.
Beeper: Activated (3 seconds, then a pause of 30 seconds) until the mute button is
pressed.
Display: Alternates message “ALL 03” with standard display
Reset: Automatically resets only when probe reading has returned to normal.
Optional probe alarm (ALL 04)
(disabled if no probe is connected)
Input SW2 (ALL 05) (door microswitch alarm)
Cause: Input active for more than 5 minutes with appliance in start status.
Door open (close door) Microswitch fault (replace the microswitch)
Beeper: Activated (3 seconds, then a pause of 30 seconds) until the mute button is
pressed.
Display: Alternates message “ALL 05” with standard display
Reset: Press the mute push-button (with beeper off).
Automatically resets if input value returns to normal Alternatively, switch off the
panel then turn it back on (stand-by).
Input SW1 alarm (ALL 06)
(Press. max - thermal-magnetic switch - Oil diff. pressure switch)
Cause: Input active for more than 5 seconds
Effect: Sets the appliance to STOP.
Reset the max. pressure switch, thermal-magnetic switch or differential pressure
switch.
Beeper: Activated (3 seconds, then a pause of 30 seconds) until the mute button is
pressed.
Display: Alternates message “ALL 06” with standard display
Reset: Press the mute push-button (with beeper off) with no alarm cause displayed