GB
23
Input SW4 alarm (ALL 07) (Automatic reset min. pressure switch)
Cause: Input active for more than five seconds when appliance in start mode
The alarm is disabled for approx. two minutes at each compressor start-up. The
alarm is disabled during “pump-down”.
If the alarm persists, contact SERVICE.
Effect: Appliance sets to STOP.
Start/Stop and Defrost push-buttons are disabled.
Beeper: Activated (3 seconds, then a pause of 30 seconds) until the mute button is
pressed.
Display: Alternates message “ALL 07” with standard display
Reset: Press the mute push-button (with beeper off).
Alternatively, switch off the panel then turn it back on (stand-by).
Input SW3 alarm (ALL 08) (Kriwan compressor automatic reset)
Cause: Input active for more than five seconds at least three times when appliance is in
start mode
Effect: Compressor shuts down and resumes operation when input value returns to nor-
mal.
The appliance sets to STOP at third alarm.
Beeper: Activated (3 seconds, then a pause of 30 seconds) until the mute button is
pressed.
Display/Led: Alternates message “ALL 08” with standard display
Reset: Press the mute push-button (with beeper off).
Alternatively, switch off the panel then turn it back on (stand-by).
Input Ht1 alarm (ALL 09) (Input in voltage 1 ... fuses).
Input Ht2 alarm (ALL 10) (Input in voltage 2 ... fuses)
Excessive temperature alarm (ALL 11)
Cause: (only during storage) cell probe constantly detects a temperature greater than the
sum of positive or negative storage set points with relative alarm delta.