6-2 Linear scale
The default values of measuring range and linear scale are set as follows for the linear input (mV, V, mA).
Measuring range (default)
Linear scale range (default)
- Setting procedure -
(1) Set the minimum and maximum values of the analog signal input from the sensor with
"Measuring range lower/upper limit (MODE5)".
(2) Check the control range (display range), and set the decimal point position and the scale
lower/upper limit with "Linear scale zero/span (MODE5)".
Example 1) Setting a control range of 0.00 to 100.00 for 0 to 20mV
Measuring range ··· Lower limit: 0.00, upper limit: 20.00
Linear scale ··········· Decimal point: DOT2, zero: 0.00, span: 100.00
Example 2) Setting a control range of 0.00 to 100.00 for 4 to 20mA (250Ω/external)
Input type ··············· ±5V
Measuring range ··· Lower limit: 1.000, upper limit: 5.000
Linear scale ··········· Decimal point: DOT2, zero: 0.00, span: 100.00