Remote Operation
Query Example: MEAS:VOLT:AC? returns the output AC rms voltage.
OUTPut
Description: This command enables or disables the AC source output.
Syntax: OUTPut[:STATe] <Boolean>
Parameters: 0 | 1 | OFF | ON
*RST Value: OFF
Example: OUTP ON enables output.
OUTP 0 disables output.
Query Syntax: OUTPut[:STATe]?
Return Parameters: 0 | 1
Query Example: OUTP? returns the output enable condition.
OUTPut:PROTection:CLEar
Description: This command clears the latch that disables the output when a short, over
current, over power, over temperature, fan fail, or under voltage condition
is detected. All conditions that cause the protection should be removed before
the latch is cleared. Then, the output remains disabled until another OUTP ON
command is received.
Syntax: OUTPut:PROTection:CLEar
Parameters: None
Example: OUTP:PROT:CLE clears the latched protection.
CURRent:
Description: This command sets the output limit current.
Syntax: [SOURce:]CURRent: LIMit[:IMMediate] <NRf+>
Parameters: 0 to 30
*RST Value: 30
Example: CURR:LIMit 15 It sets the output limit current to 15A.
CURR:LIMit MAX It sets the output limit current to maximum value.
Query Syntax: [SOURce:]CURRent: LIMit[:IMMediate]?
Return Parameters: <NR2>
Query Example: CURR:LIMit? It returns the set value of output limit current.
6-11