| INSTALLATION MANUAL PRORAPID
Possible error messages Notes for the specialist
Sensor x defective
Means that either the sensor, sensor entrance on the
controller or the connecting wire was defective
(See “ Temperature Resistance Table for Pt1000 Sensors “
on page 9).
Restart
Means that the controller was restarted, for example, due
to a power outage. Check date & time!
Time & Date
This display appears automatically after a longer network
disruption, because the time & date must
be examined and, if applicable, adjusted.
Frequent on / o
A relay was switched on and o more than 5 times within
5 minutes.
Anti-legionella failed
Anti-legionella failed appears if at least anti-legionella Tsoll
-5 °C could not be held at the antilegionella
sensor for the set exposure time.
Tips
The service values include not only
current measurement values and
operating states, but also all of the
settings for the controller. Write the
service values down just once after
commissioning has been successfully
completed.
In the event of uncertainty as to the
control response or malfunctions
the service values are a proven
and successful method for remote
diagnosis. Write the service values
down at the time that the suspected
malfunction occurs. Send the service
value table by fax or e-mail with a brief
description of the error to the specialist
or manufacturer.
To protect against loss of data, record
any statistics and data of particular
importance at regular intervals.