SM-A20758-A/3 1. PRODUCT OVERVIEW
17 2020-10-06
Individual specification
Index
Sub
index
Item
Value
Data
storage
Access
Data
length
Format
0x0100
0
Control stop function at
zero input signal
0 OFF
1 ON
Y
R/W
2 byte
UInteger16
0x0101
0
Switch output 1
Mode Selection
0 OFF
1 Mode 1
2 Mode 2
Y
R/W
2 byte
UInteger16
0x0102
0
Switch output 2
Mode Selection
0 OFF
1 Mode 1
2 Mode 2
Y
R/W
2 byte
UInteger16
0x0103
0
Switch output 1
Mode 1 Lower limit value
0
Setting range 0 to 50
Y
R/W
2 byte
UInteger16
0x0104
0
Switch output 1
Mode 1 Higher limit value
0
Setting range 0 to 50
Y
R/W
2 byte
UInteger16
0x0105
0
Switch output 1
Mode 2 Lower limit value
Note 1
0
Setting range 0 to 90
Y
R/W
2 byte
UInteger16
0x0106
0
Switch output 1
Mode 2 Higher limit value
Note 1
100
Setting range 10 to 100
Y
R/W
2 byte
UInteger16
0x0107
0
Switch output 2
Mode 1 Lower limit value
0
Setting range 0 to 50
Y
R/W
2 byte
UInteger16
0x0108
0
Switch output 2
Mode 1 Higher limit value
0
Setting range 0 to 50
Y
R/W
2 byte
UInteger16
0x0109
0
Switch output 2
Mode 2 Lower limit value
Note 1
0
Setting range 0 to 90
Y
R/W
2 byte
UInteger16
0x010A
0
Switch output 2
Mode 2 Higher limit value
Note 1
100
Setting range 10 to 100
Y
R/W
2 byte
UInteger16
0x010B
0
Proportional value setting
0 OFF
1 Proportional value
increase
2 Proportional value
down
Y
R/W
2 byte
UInteger16
0x010C
0
Proportional value level
down setting
1
Setting range 1 to 10
Y
R/W
2 byte
UInteger16
0x010D
0
Automatic power off
setting
0 OFF
1 ON
Y
R/W
2 byte
Integer16
0x010E
0
Key lock setting
0 Unlock
1 Lock
Y
R/W
2 byte
Integer16
0x010F
0
Input setting
0 Normal Mode
1 Preset Mode
2 Direct Mode
Y
R/W
2 byte
Integer16
0x0110
0
Preset memory 1
0
Setting range: Depends
on the pressure range.
Y
R/W
2 byte
Integer16
0x0111
0
Preset memory 2
0
Setting range: Depends
on the pressure range.
Y
R/W
2 byte
Integer16
R: read, W: write, R / W: read / write
Default value
Note 1: In using Mode 2, set so that the Higher limit value is greater than or equal to “Lower limit value +10”. If this condition is not
satisfied, the SW output will always be OFF.