TSM/TSL Vertical Stack
Rev.: January 18, 2021
THE SMART SOLUTION FOR ENERGY EFFICIENCY
ECM-CV Blower Performance Data
Table 5: TSM/TSL with ECM-CV Motor
Airow in CFM with wet coil and clean 1” berglass air lter.
All units AHRI/ISO/ASHRAE 13256-1 rated on CFM shown on performance data page.
If unit is dual voltage rated, then the airow is rated at the lowest voltage, i.e. 208V for 208-230V units.
Shipped on default settings. C=Cooling; H=Heating; D=Dehumidication
Change from default setting with Service tool (ACDU03C) or Communicating thermostat (ATC32U03C).
Airow is controlled within 7%, up to the max ESP.
TSL15-36 ramp default is 30 sec.
* - Stage 2 ECM CV motor speed is engaged with a thermostat Y2 call. TSM Series is only available with single-stage compressors.
Tranquility
Model
Setting
Cooling Mode Heating Mode Dehumid Mode
Continuous
Fan Only
Mode
Fan Motor
Stage 1
Fan Motor
Stage 2*
Fan Motor
Stage 1
Fan Motor
Stage 2*
Fan Motor
Stage 1
Fan Motor
Stage 2*
TSM/L09
Default 250 350 250 350 250 300 250
Min 250 250 250 250 250 250 250
Max 400 400 400 400 400 400 400
TSM/L12
Default 300 400 300 400 300 350 300
Min 300 300 300 300 300 300 300
Max 500 500 500 500 500 500 500
TSM/L15
Default 500 600 500 600 500 500 500
Min 500 500 500 500 500 500 500
Max 700 700 700 700 700 700 700
TSM/L18
Default 600 700 600 700 600 600 500
Min 600 600 600 600 500 500 500
Max 800 800 800 800 800 800 800
TSM/L24
Default 650 850 650 850 650 650 600
Min 650 650 650 650 600 600 600
Max 950 950 950 950 950 950 950
TSM/L30
Default 850 1000 900 1000 850 850 700
Min 850 850 900 900 800 800 700
Max 1100 1100 1100 1100 900 1100 1100
TSM/L36
Default 900 1200 900 1250 900 900 900
Min 900 900 900 900 900 900 900
Max 1250 1250 1350 1350 1250 1250 1250