TSM/TSL Vertical Stack
Rev.: January 18, 2021
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Blower Performance Data – TSL09
Table 5h
External Static Pressure (in. wg)
PSC - High Static
Speed Tap 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Low
RPM 1000 1120 1210 1290 1380
Power (W) 145 139 132 125 119
CFM 350 340 320 290 270
Medium
RPM 1520 1570 1610 1650
Power (W) 162 151 139 127
CFM Operation not recommended 430 390 340 280
High
RPM 1710
Power (W) 151
CFM 390
ECM - Constant Torque
Speed Tap 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
1
RPM 980 1080 1170 1260 1360
Operation not recommendedPower (W) 47 51 54 58 62
CFM 340 320 290 270 240
2
RPM 1060 1160 1230 1320 1390 1500
Power (W) 58 62 66 70 75 79
CFM 380 360 330 310 280 260
3
RPM 1230 1310 1390 1440 1530 1590 1650
Power (W) 79 84 88 92 97 101 105
CFM 400 380 360 340 320 290 270
4
RPM 1470 1480 1550 1630 1680
Power (W) Operation not recommended 108 113 117 122 126
CFM 410 390 370 360 340
ECM - Constant
Volume
CFM 0.1 0.2 0.3 0.4 0.5 0.6 360 340
250
RPM 810 950 1100 1230 1370 1490 1560 1640
Power (W) 30 38 47 57 67 78 89 101
300
RPM 900 1050 1180 1300 1410 1520 1590 1660
Power (W) 38 48 58 69 81 93 105 118
350
RPM 1000 1140 1260 1380 1450 1540 1620 1690
Power (W) 50 62 73 85 98 110 124 137
400
RPM 1100 1230 1340 1450 1490 1570
Power (W) 65 79 92 105 119 132
All data is presented as lowest of nameplate voltage.
All data is shown wet coil with clean 1" lter.
All data is ran at 80°F DB and 67°F WB.
CFM Tolerance is 7%
RPM/Watt Tolerance 10%