Blower Performance Data – TSL12
Table 5i
All data is presented as lowest of nameplate voltage.
All data is shown wet coil with clean 1" lter.
All data is ran at 80°F DB and 67°F WB.
CFM Tolerance is 7%
RPM/Watt Tolerance 10%
External Static Pressure (in. wg)
PSC - High Static
Speed Tap 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Low
RPM 980 1090 1190
Operation not recommendedPower (W) 145 139 132
CFM 350 340 320
Medium
RPM 1290 1360 1440 1470 1540 1590
Power (W) 197 185 174 162 151 139
CFM 500 480 460 430 390 340
High
RPM
Operation not recommended
1590 1630 1680
Power (W) 151 151 151
CFM 520 470 390
ECM - Constant Torque
Speed Tap 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
1
RPM 1070 1140 1230 1320 1400
Operation not recommendedPower (W) 66 70 74 78 82
CFM 410 380 360 330 310
2
RPM 1140 1190 1280 1370 1430 1510 1580
Power (W) 54 58 61 65 69 73 77
CFM 450 420 400 380 360 330 310
3
RPM 1190 1240 1320 1400 1450 1530 1590 1660
Power (W) 79 83 87 91 96 100 104 108
CFM 480 460 440 420 400 370 350 330
4
RPM
Operation not recommended
1580 1630 1690
Power (W) 137 141 145
CFM 480 460 440
ECM - Constant Volume
CFM 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
300
RPM 890 1040 1170 1300 1400 1500 1570 1660
Power (W) 38 48 58 69 81 93 105 118
350
RPM 980 1100 1220 1340 1430 1520 1590 1670
Power (W) 50 62 73 85 98 110 124 137
400
RPM 1060 1170 1280 1380 1450 1540
Power (W) 65 79 92 105 119 132
450
RPM 1140 1230 1330 1430
Power (W) 87 101 115 128 Operation not recommended
500
RPM 1220