36 CSRN-XHE2 15.2-44.4 M08F40N15-02
10.4 Immersed electrode humidier
SUPPLY WATER
The humidier must be supplied with mains water having the following features:
t
pressure between 0.1 and 0.8 Mpa (1 – 8 bar)
t
temperature between 1 and 40°C
Do not use:
t
water treated with softeners: it can corrode the electrodes and form foam with possible faults/malfunctionings
t
pit, industrial or potentially polluted (chemically or bacteriologically) water
t
disinfectants or anti-corrosive substances mixed with water, as potentially irritating
Supplying the humidier with water treated with reverse osmosis ltering system gives the following advantages:
t
reduces limescale deposits
t
reduces energy consumptions
t
reduces maintenance costs
t
increases humidier duration
Check that the lter guarantees a water ow rate higher than the ow rate of the installed humidier.
DRAINAGE WATER
It can reach a temperature of 100°C
It contains the same substances of the supply water but in higher concentration.
As it is not toxic, it can be disposed of with white waters.
Periodical checks
Do not use solvents or detergents to clean the plastic components.
For descaling use a vinegar or acetic acid solution at 20%, subsequently rinsing with water.
15 days
Cylinder:
not over 300 hours of work
checking operation, general state, no leaks
90 days
Cylinder:
not over 1000 hours of work
checking operation, general state, no leaks, any replacement
1 year
Cylinder:
not over 2500 hours of work (disposable cylinders)
Load solenoid valve replacement:
disconnect electric power supply, dismantle valve, clean the lter
Drain solenoid valve:
disconnect electric power supply, remove reel and dismantle valve body and any impurity and rinse
The power supply bowl, piping:
check they are free and without impurities
5 years
Cylinder:
not over 10000 hours of work (inspectional cylinders)
replacement

Table of Contents