19
5 - ELECTRICAL CONNECTIONS
It is possible to automatically change the set-point according
to the outside temperature.
Enable the function:
Par dS00 set-point compensation of the outside
temp.
0 = Disabled
1 = Proportional
2 = Fixed (by step)
5.11 WATER SET POINT COMPENSATION WITH EXTERNAL TEMPERATURE
Main menu
Parameters
dS
dS00
Parameter modification
COOLING
t ext °C
dS01 < 0
dS03
dS05
Setpoint
dynamic
differential
Example :
dS01 = - 6°C
dS03 = 4°C
dS05 = 36°C
setpoint = 10°C
Compensated setpoint = 14°C
t ext °
C
36°C
30°C
14°C
10°C
setpoint
Cool description
dS01
Differential proportional zone in Cool on external air
dS03
Max water set dynamic differential in Cool
dS05
Set point dynamic differential of external air
With low ext. temperature the refrigerant requirements are
reduced.
The internal comfort can also be obtained with a set-point
higher than standard.